Installation manual
Introduction
7
station. The device can be connected to the control panel loop via an input/output module (not included),
installed inside the box, or by means of the RS485 BUS, thus allowing the complete supervision of the
power station and control of the 3 outputs.
[D] SmartLine-EXT fire-extinction panel (optional)
SmartLine-EXT fire-extinction panels are based on SmartLine conventional fire detection panels (4-zones).
These control panels provide all the functions of SmartLine conventional fire-detection panels plus 1
SmartLetLoose/ONE extinction channel.
They interface with SmartLoop control panels via a built-in RS485 BUS. It is possible to programme the
SmartLine-EXT fire-extinction control panel to activate its functions in response to “local” data/signals
(conventional zones, extinguishant terminals, Stop extinction, etc.), or in response to “remote” data/
signals coming from the SmartLoop control panel.
[E] Sounderflashers
These audible/visual signaling devices connect to the control panel outputs and activate when specific
conditions occurs. The cause of activation (alarm, pre-alarm, early warning, etc.) can be defined during the
system configuration phase.
1.2
Other parts of the system
Point:
synonym and definition of a loop device (detector, etc.).
Zone:
a group of points (detectors, etc.). The points can be assigned to the zones during the configuration
phase. Consult your local Fire code for the rules regulating automatic fire detection installations and for full
details regarding zone limitations.
Power Supply
: a module, connected to the mains 230 Vac, that provides a stabilized voltage @ 24 V
(27.6 V) to the system and the charge source to the batteries. The EN54-4 compliant power-supply module
is housed below the motherboard. The mains voltage (230 Vac) is the primary power source of the system.
Refer also to paragraph
7.18 Connecting the mains power source
.
Batteries:
the secondary power source of the system. The panel houses two lead batteries @ 12V 17Ah
(connected in series). The system monitors the battery status (efficiency and charge). In the event of
inefficient or low battery conditions, the system will signal battery fault. If primary (230 Vac) power failure
occurs, the batteries will take over, however, they will shutdown automatically if the blackout persists. The
automatic battery shutdown feature prevents irreparable damage to the batteries. Refer also to paragraph
7.16 Batteries
.
Thermal probe:
an accessory tool, to be connected to the panel and attached to the battery pack. This
device monitors the temperature of the external battery pack and regulates the battery charge accordingly.
Refer also to paragraph
7.17 Connecting the thermal probe
.
RS485 Bus:
4 wire BUS for the Repeater connections. Four pole twisted shielded cable must be used for all
connections. Refer also to paragraph
7.10 Connecting devices to the RS485 BUS
.
Timer:
a logical entity (the panel provides 8 timers) for automatic time-management of preset intervals (2
intervals per day) on preset days of the week and specific dates. The timers can be used in equations and/
or to manage predefined operations.
Equation:
a group of logical conditions defined by the installer. An equation comprises a series of
operators (AND, OR, +, etc.) and a series of operands (Points, Zones, Timers, etc.). An equation can be
associated with an output that will activate when the equation is satisfied.
Holidays:
a list of days defined during the system configuration phase that can be associated with the
timers.
Early Warning:
a signal generated by detectors with the early-warning feature (to be defined during the
system configuration phase). The detector senses for a level of smoke or heat that exceeds its early
warning threshold (each detectors can be set separately). This signal indicates that the person/s
responsible for the safety of the building and its occupants should verify the alarm or check the
functionality of the detector concerned.