26
Accessory devices
Installation manual
5.3
The SmartLetUSee/LCD and SmartLetUSee/LED Repeater panels
The SmartLoop fire control panel supports 14 SmartLetUSee/LCD remote Repeater panels. These remote
panels can be connected to the RS485 bus on the motherboard by means of a 4-pole cable. Repeater
panels replicate all the SmartLoop fire system data and allow authorized personnel to access and control
the system in accordance with access authorization (access requires code entry).
The repeater motherboard is located on the frontplate of the device, therefore, when you open the repeater
enclosure the reverse side of the motherboard is on view. The following is a description of the parts used
during the installation phase:
Figure 15 - The SmartLetUSee/LCD module
You can connect a SmartLetUSee/LED module to each SmartLetUSee/LCD module by means of the
connection wire supplied with the module. The SmartLetUSee/LED provides 48 zone-status LEDs. The On/
Off of each LED can be configured individually during the programming phase.
Note:
The SmartLetUSee/LED module can be used only in combination with a SmartLetUSee/LCD module.
Figure 16 - The SmartLetUSee/LED module
[A]
SmartLetUSee/LCD
Front of module
[B]
SmartLetUSee/LCD
Back of board
[C]
DIP switches
To set the repeater address
[D]
RS485 Terminals
From the bottom of the figure to the top “
+24V - + GND
”; for the connection
to the RS485 BUS
[E]
EOL Terminals
These terminal are for the setting jumper and, depending on the position of the
setting jumper, indicate the position of the repeater in the system.
[F]
SmartLetUSee/LED Terminals
Connector for the SmartLetUSee/LED module