Connections
Installation manual
Figure 26 - Connecting the SmartLoop/INOUT module
7.13
Connecting to a PC
The panel can be connected:
• permanently to a PC equipped with monitoring software;
• temporarily to a PC during system configuration sessions (for uploading/downloading).
The panel can be connected via:
• RS232 port
• USB port
• Ethernet port (if the system is equipped with a SmartLinkLAN board)
Note:
Use of one of these ports automatically excludes use of the others.
The communication ports are opto-isolated in order to allow permanent connection to a PC or printer.
If the connection is through the USB port, the system may ask for the installation driver when the USB
cable (LINKUSBAB accessory item) is first inserted. The driver is included in the SmartLeague software
programme which, once installed, can be found in the following folder:
C:\Program files\Inim\SmartLeague\Drivers\
[A]
Supervised NAC Output
[B]
Conventional Zone
[C]
Gas Zone
Lines configured as Gas Zone 4-20mA will generate an “early warning” signal if the value of the
detector output exceeds 12mA, and an “alarm” signal if the value of the detector output exceeds
16mA.
In order to implement the “early warning” signal, it must be enabled (during the programming
phase) on both the control panel and the zone the line belongs. The “early warning” signal will stop
automatically, if a gas detector exceeds the 12mA “early warning” threshold then returns below this
value without reaching the “alarm” threshold.
[D]
Supervised Input
C
BROWN
BLACK
RED
GOLD
SmartLoop
control panel
Gas
detector
4-20mA
D
YELLOW
VIOLET
ORANGE
GOLD
BROWN
GREEN
ORANGE
GOLD