Installation manual
Connections
37
7.14
Connecting a SmartLAN (or SmartLAN/SF) equipped control panel to a PC
In this case, the RS232 and USB port will not be available for use. Therefore, the PC must be connected
directly to the Ethernet port of the SmartLAN board or through a network switch by means of an inverted
patch-cord.
The default IP address is 192.168.1.92
Consequently the integrated Ethernet board of the PC must be configured with an IP of the same class (e.g.
192.168.1.46). Once the configuration phase is complete, you will be able to open your browser and enter
the SmartLAN board address:
http://192.168.1.92
7.15
Connecting a serial printer
1. Connect the serial printer to the RS232 port.
2. From the panel, access the main menu and select
Printer Settings
3. Enable the printer to communicate with the panel
Note:
If you intend disconnecting the serial printer from the RS232 port in order to connect a PC, it will be
necessary to DISABLE the serial printer before doing so. If you do not DISABLE the serial printer, the PC
will be unable to communicate with the panel.
7.16
Batteries
The panel enclosure provides housing for two 12 V/17 Ah internal batteries.
Use YUASA batteries, model NP 17 -12 FR or similar with UL94-V2 flame class (or higher).
Once powered up, the panel will recharge and monitor the batteries automatically, as follows.
7.16.1 Efficiency testing
The panel checks the efficiency of the batteries at 60 second intervals, by simulating load current demand
(as required during mains black-out). If the battery results inefficient, the condition will be signalled on the
respective fault LED on the frontplate and also on the display.
7.16.2 Voltage testing
The panel continuously monitors the battery voltage. If the voltage drops below the 22.8 V, the panel will
signal the event on the respective fault LED and on the display. The event will end when the voltage
restores to over 24.6 V.
7.16.3 Deep discharge monitoring
If the battery voltage drops below 18 V, the panel will disconnect them in order to avoid battery damage. If
this occurs, the PL terminal will close to ground thus generating a “Shutdown” signal.
7.16.4 Connecting the batteries
1. Locate the batteries inside the panel enclosure.
2. Using the battery wire (Figure 27 - [A]), connect the batteries together.
3. Using the battery terminal eyelet wires (included), connect the battery (Figure 27 - [B]).
Attention:
Ensure that connector polarity is correct.
4. Connect the battery wire connector (Figure 27 - [C]) to the control panel (paragraph
4.2 - [R]
).
Attention:
Ensure that connector polarity is correct.
Содержание SmartLoop Series
Страница 58: ...58 Notes Installation manual Notes ...
Страница 59: ...Installation manual 59 ...