Installation manual
Argus Devices
51
B.4
Device Consumption
B.5
Configuring Argus devices
Every ARGUS device requires an address to identify it in the loop. You can address ARGUS devices by
either using a VPU (Vega Programming Unit) or by means of the Auto-addressing option.
B.5.1
Auto-addressing from panel
At the SmartLoop panel keypad:
1. Press any key to access the Main menu.
2. Select
Programming
,
<code>
,
Configuration
,
Modify Configuration
,
Manual Configuration
,
Loop
3. Select the Loop to be configured (1 - 8).
4. Select the loop parameters. The respective loop parameter screen will be shown:
Figure 33 - Loop parameters
5. Program the loop in accordance with the connected device type and circuitry (2 or 4 wires).
6. Press the
button to confirm the setting and exit the screen
Note:
If you exit the screen using the
Esc
button, the setting WILL NOT BE SAVED!
7. Press
Esc
repeatedly until you return to the Programming menu.
8. Select
Configuration
,
Modify Configuration
,
Auto Enroll
,
Loop
Figure 34 - Loop programming screen
9. Enter a “
+
” sign in the programming field that corresponds to the loop concerned.
Use the cursor keys
S
and
T
to select/deselect the options and cursor keys
W
and
X
to move from one
loop to another.
If you select “Auto-configuration”, the control panel will enroll the devices connected to the loop using
the pre-assigned address (assigned by means of the VPU100) without making changes to the devices
enrolled during previous operations.
If you select the “Re-addressing” option, the previously assigned addresses will be deleted and new
addresses will be given. All previously programmed data will be cleared.
10. Press
- the panel will show the summary screen and ask for permission to continue.
11. Press
to start the “Auto-configuration” phase.
B.5.2
Addressing detectors using the VPU100
Work carefully through the following steps:
1. Remove the detector from its base (twist off).
Device
in stand-by
in alarm
Detectors
90
P
A
6 mA
Modules
120
P
A
6 mA
L o o p f i r m w a r e v e r s i o n : 1 . 0 0
< L o o p n >
L o o p T y p e : A R G U S
L o o p W i r i n g : 4 W i r e s
L o o p N . 1 2 3 4 5 6 7 8
E N R O L L D E V I C E S : . . . . . . . .
R E - A D D R E S S A L L . : . . . . . . . .