Installations of the SmartLoop\NET board will allow you to create a network of up to 30 control panels
(refer to Installation Manual paragraph 4.4 The SmartLoop/NET board). Once each control panel has
been properly installed, you must assign its network address (each address must be assigned using
the control panel concerned).
The network control panels pass data through the network in such way as to allow each control panel
in the network to manage the data of all the others. This allows the operator to be at one control
panel, view the real-time status of all the others and implement remote commands (reset, silence).
Working directly from the control panel, you can program the parameters that include it in the
network, and make it as the system clock.
24.1 Programming the SmarLoop\NET board
FROM COMPUTER
Go to SmartLoop System, Control panel x, SmartLoop\NET, System Programming
24.1.1 Parameters
FROM PANEL
<any key>,
8 Programming, <code>,
5 NETWORK Programming,
or
<any key>,
8 <code> 5
You can set the parameters that put a control panel in the network, and make it the system clock
directly from the control panel concerned. The control panel address must have already been assigned
by means of the Network or Complete AUTO Configuration option (refer to Chapter 7 - Initialising the
configuration/programming from panel):
Press keys and
to scroll the
parameters list.
Press to confirm and step back to the
previous menu.
Press ESC to quit without saving and step back to the previous menu.
Panel address
The address can range from 1 to 30 and must be assigned directly at
the control panel. Control panels with address 00 will be excluded
from the network.
Broadcast events from
The control panel transmits its events to the other control panels in
the network in accordance with the specified priority (level of
importance).
Check emergency wiring
integrity
If you enable this option, control panel will check the wiring of the
emergency line.
Panel Number
Addresses of control panel
Panel Description
Control panel description
Accept broadcasted events from
The control panel accepts events from other control panels in
accordance with the specified priority (level of importance).
Accept Reset from remote panel
The control panel can be reset by selected control panels in the
network.
Accept Silence from remote
panel
The control panel can be silenced by selected control panels in the
network.
P a n e l c o n f i g u r e d i n t h e n e t w o r k a s
A d d r e s s : 0 0
E v e n t b r o a d c a s t o v e r n e t w o r k