Programming Manual
Programming the control panel
45
14.4.1 Parameters
14.4.2 Control Equations
This section will allow you to define an equation whose logical result (TRUE/FALSE) activates or
deactivates the group.
The equation interprets the status of the systems groups and timers (TRUE/FALSE):
• as logical operands:
In example ‘A’ the condition will be TRUE if
both group 2 and group 3 are active or only
timer 1 is active and timer 7 is not active.
In example ‘B’ the condition will be TRUE if
the logical values of group 2 and group 3
are different.
• as numeric operands in which the logic value TRUE is intended as numeric value ‘1’:
In the example the group will be active
when at least two of the four groups are
active.
The number ‘2’ has been included as a
constant.
Select Control equation to check the balancing of the brackets.
Note:
In order to read an equation, leave the cursor on the operand: the description details will appear.
FROM PANEL
Not available.
Enable
Enable/Disable the group.
Activation Delay
The delay will be applied when the defined condition occurs. The delay will be
applied even if the group is activated by a zone signal.
Type
Pulse: the group will activate when the condition occurs and deactivate at the
end of the Activation Time. If you have deselected Always finish
Activation Time, the group will deactivate when the condition clears.
Bistable: the group will activate when the condition occurs and deactivate
when the condition clears.
Activation Time
Activation time of groups with the Pulse attribute
Always finish Activation
Time
Only for groups with the Pulse attribute. If this option is deselected, the group
will deactivate if the condition clears before the end of the Activation Time. If
this option is selected, the group will deactivate at the end of the Pulse
length.
Actions on Activation/
Deactivation
To associate with status change, also the operating mode of the control panel.
e.g. A: (((C01G02 AND C02G03) OR T01) NOT T07)
e.g. B: (C01G02 XOR C02G03)
e.g. (( C02G04) > 2)