Installation Guide
INGENIA MOTION CONTROL
Confidential and proprietary information.
Unauthorized Copies Prohibited.
Page
of
154
307
Motor choke
In applications where electromagnetic compatibility is a concern or that must comply with the EMC standards, the use of an external common modechoke is
necessary. Place the choke as close to the driver as possible. 2 turns to the choke are recommended for best performance. Make sure the chosen choke does not
saturate at the maximum operating phase current. If this happens, the choke temperature would increase rapidly.
Next table shows a choke that fits the Jupiter Servo Drive specifications.
Type
Manufacturer
Reference
Output Choke
Emikon
High current wiring recommendations
Wire section
The minimum wire section is determined by the supply and motor current. It is preferred to use wide section stranded wires to reduce impedance, power losses and
ease the assembly. Insulator size should not exceed 6.35 mm (connector pitch). Following table indicates recommended section:
Connection
Minimum wire size
Maximum wire size
Stranded wire (preferred)
2 mm
2
4 mm (12 AWG)
2
Solid wire
3 mm
2
6 mm (10 AWG)
2
Wire ferrules
It is recommended to use wire ferrules to prevent cable damage or wrong contacts. Ensure crimped ferrule diameter does not exceed 2.5 mm and the insulator is <
5 mm. Following are some suggested ferrules: