User Manual V1.1a | XtracontrolEC22
Operating mode: voltage input AI (I)
Feature
Value
Description
Connections per input
–
AI (I) and AGND;
connect screening with AGND.
Protection
–
Thermal current limitation
Measuring range
–20 to +20 mA
Technical current direction into AI (I)
Load impedance
typ. 20 Ω
–
Max. errors at 25°C
±0.2% (±80 µA)
–
Temperature coefficient
±40 ppm/K
(±0.8 µA/K)
–
Digital resolution
24 bit
–
Data format in
user program
32 bit real
(floating-point number) in milliamps (mA)
Maximum permissible
permanent overload
Max. ±25 mA
–
Output of digital value
in case of overload
–
If a current greater than ±20 mA flows into an AI (I),
a plausible value is still given up to approx.
±25 mA.
The specified accuracy is only valid for the range –
20 to +20 mA.
Input type
–
Current measurement compared to AGND
Reference potential
AGND
–
Dynamic characteristics
Analogue filtering
Second-grade low-pass
filter; time constant
T = approx. 215 µs
–
Greatest temporary
deviation during
electrical error testing
according to
IEC 61131-2
0.5% of measuring
range
–
Operating mode: temperature inputs AI-PT
Feature
Value
Description
Connections per input
–
Sensor connection between AI (U/T) and AGND
Possible sensors
PT100 and PT1000
acc. to EN 60751
Accuracy class AA, A, B and C platinum sensors may
be used; recommendation: B or C
Measuring range
–40 to +200°C
–
Measuring current
(RMS)
0.3 mA
–
Conversion time
250 ms
–
Max. errors at 25°C
±0.21% (±0.5°C)
–
Temperature coefficient
±50 ppm/K
(±0.012°C/K)
–
Digital resolution
24 bit
–
Data format in
user program
2 × 32 bit real
(floating-point number) in Ohms (Ω) and degrees
Celsius (°C)
Linearisation
–
The value in degrees Celsius is calculated from the
resistance value and linearised (3
rd
degree polynomial)
Input type
–
2-wire measurement or 3-wire measurement
Reference potential
AGND
–
© Infranor GmbH
27