User Manual V1.1a | XtracontrolEC22
Data of the analogue inputs
Data of the analogue inputs
Feature
Value
Description
Cable length
max. 30 m
Only valid for unshielded connection cables
Cables over 30 m in length must be shielded
Modulation method
Delta-sigma modulation
–
Shared points between
the channels
AGND reference
ground
–
Calibration frequency
12 months
Maintenance of accuracy class
Clamp arrangement
Shielding on common
AGND pins
–
Sampling duration/rate
for measuring values
1 ms
A reading is taken from each input channel every
millisecond, regardless of how many channels are
actually in operation.
Sampling rate
Operating mode AI-PT
250 ms
In operating mode AI-PT, calculations are carried
out after the millisecond sampling rate. A new
value is available in the user program every
250 ms.
Digital filtering
Possible
filter settings
Time range for averaging
Time range for averaging
Operating mode AI-PT
10
10 ms
2,5 s
100
100 ms
25 s
1000
1000 ms (1 s)
250 s
If filtering is active, an average is calculated for the set time range. However a value is still issued during the
sampling rate interval. For example, if the filter is set to 1,000, the average of the measurements for the previous
1,000 ms / 1,000 measurements is issued each millisecond (or, in the case of operating mode AIPT, the average for
the last 250 ms / 1,000 measurements).
The filtering can be activated and configured using CODESYS V3. The sampling rate is constant. It can only be
filtered with a whole multiple of the sampling rate.