26
-
ALARMS MENU
___________________________________________________________
The most important function of the STS is alarms menu. There is a real time clock in the STS and STS records
all events by their date and time. And the user can see all previous events and alarms, by order. Every log
record contains 24 alarms and 10 status messages.
000>101003 10:30
This is the last recorded alarm on 10-10-2003 date, at 10:30 and the event number is 000.
The second line shows alarm or alarms time shared by order which were recorded at that time.
If the user presses the left or right buttons, the event numbers will change from 000 to 127, 000 is the last event
and the 127 is the first (oldest).
<ENTER> CLEAR LOG:
If the user press enter key during this message, STS will clear all recorded events
from memory.
Note : For log table delete service login is required otherwise the user can not clear log events.
S1 CODE: 000
This message shows the detailed alarm codes for Source1. The numbers are arranged as
Bitmap and the meanings are as follows:
Code
Description
Code:0
No alarm on Source 1, Source normal
Code:1
Source 1 input voltage out of tolerant
Code:2
Source 1 phase sequency bad
Code:4
Source 1 backfeed tripped
Code:8
Source1 black-out sense
Code:16
Source1 phase balance bad
Code:32
Source1 frequency is out of tolerance
Code:64
Source1 input switch is off
Code:128
phase or alternance loss on S1
At some cases numbers can be shown as total (contains more then 1 alarm at the same time)
S2 CODE: 000
This message shows the detailed alarm codes for Source2. The numbers are arranged as
Bitmap and the meanings are as follows.
Code
Description
Code:0
No alarm on Source 2, source normal
Code:1
Source 2 input voltage out of tolerant
Code:2
Source 2 phase sequency bad
Code:4
Source 2 bacfeed tripped
Code:8
Source2 black-out sense
Code:16
Source2 phase balance bad
Code:32
Source2 frequency is out of tolerance
Code:64
Source2 input switch is off
Code:128
phase or alternance loss on S2
At some cases numbers can be shown as total (contains more then 1 alarm at the same time)
<ENTER> EXIT
If the user press ENTER button exits from alarms menu to upper menu
Содержание InfoSTS