Switching From Maintenance Bypass To Normal Operation
1) Turn on input switches S1 and S2
6) Check that the manual XFER switch S6 is on the
maintenance source side, and follow that the
corresponding static switch (either SS1 or SS2) is
turned on
3) Turn on the output switch S3
4) Change the position of the maintenance bypass switch S4
to “0”, lock it again
5) Turn manual XFER switch to “AUTO”
position
6) See there is no alarm message on LCD display if there is
no alarm unit is in normal operation mode again