Switching To Maintenance Bypass Position From Normal (automatic) Operation
1) Select the input source which is going to supply the
load during maintenance, and turn the manual
XFER switch S6 to this selected source (either
Source 1 or Source 2)
2) Follow on the mimic diagram that the load is
switched to the source selected by the manual
XFER switch S6
3) Then turn the Maintenance Bypass Switch (S4) to
the selected source for maintenance. See the
maintenance bypass message on the LCD panel
4) Turn off the output switch S3. This switch
disconnects the static transfer switches SS1 and
SS2 from the STS output, but the load continues to
work on maintenance bypass line
5) Turn off the input switches S1 and S2
6) Now, the unit is ready for maintenance