MEASURES MENU _________________________________________________________
SP1:230 240 235V
SP2:240 220 215V
LD%:045 060 015%
OPI:025 120 080A
TEMP:26C
S1-FREQ:50.2 Hz
S2-FREQ:50.1 Hz
SYNC.ANG:001 Deg
PSP1:16.1 2:16.3
<ENT>EXIT
Use down button to move on submenu
From this menu users can see all measured parameters on STS ,the submenu items are listed as follows by
order of appearance.
SP1:220 230 235V
This menu item shows Source 1 input voltages, 3 numbers shows 3 phase voltages from line to neutral as AC
volts
SP2:220 230 235V
This menu item shows Source 2 input voltages, 3 numbers shows 3 phase voltages from line to neutral as AC
volts.
LD%:045 050 060%
This menu item shows the output load percentage of STS for each output phase. 100% is maximum capacity of
STS. If the load is above 100% the STS gives overload message.
OPI : 090 100 120A
This menu item shows the output currents of STS for each of the three output phases.
TEMPER : 030 C
This menu item shows the cabinet inside temperature of the STS.
S1-FRQ : 50.1 Hz
This menu item shows the Source 1 input frequency in Hertz
S2-FRQ : 50.1 Hz
This menu item shows the Source 2 input frequency in Hertz
SYNC.ANG: 001 Deg
This menu item shows the phase difference between the two input sources in terms of angular degrees. Zero
value shows that two input sources are fully synchronized to each other.
PSP1=16.2 2=16.1
This menu item shows the two redundant DC power supply output voltages of the STS separately as DC volts.
<ENTER> EXIT
If the user press ENTER button exits from measures menu to upper menu.