9
-
INSTALLATION
ALL THE OPERATIONS DESCRIBED IN THIS SECTION MUST BE CARRIED OUT EXCLUSIVELY BY
QUALIFIED STAFF.
The company may no be held liable for any damage caused by incorrect connections or by operations
that are not described in this manual.
STORAGE OF THE STS
The storage area must have the following characteristics
Temperature : -10 to +50 C
Relative humidity : 95% max.
PREPARATION FOR INSTALLATION
PRELIMINARY INFORMATION
Model
STS450
STS4100
STS4150
STS4200
STS4300
STS4400
Nominal current
50
100
150
200
300
400
Operating temperature
0 – 40 C
Non operating temper.
-10 to + 50 C
Max. relative humidity
90% (non-condensing) during operation
Max. installation height
1000 m at nominal current rating
Dimensions WxDxH
685x530x1500 mm
685x580x1770 mm
Weight
175 Kg
205 Kg
220 Kg
240 Kg
Protection level
IP20
Cable input
From base / on front
Communication
RS232 standard - TCP/IP option
Flying transfer
Available - Standard
LCD panel and mimic
Available - Standard
Backfeed protection
Available - Standard
Software management
Available - Standard
DRY contact outputs
Available - Standard
EPO input
Available – Standard ( NO)
<X> letter on table shows 3 pole or 4 pole model options ( 3 = 3 pole , 4 = 4 pole )
ELECTROMAGNETIC COMPATIBILITY
This static transfer switch (STS) conforms to the class C2 specifications (in accordance with the provisions laid
down by the EN62040-2 standard: STS – EMC requirement). In the home environment ,it may cause radio
interference. The user may have to take supplementary measures.
This product is designed for professional use in industrial and commercial environments . Connections to the
RS232 connectors should be made with the cables provided or ,in any case, with shielded cables less than 3
meters long.
INSTALLATION ENVIRONMENT
When choosing the site in which to install the STS , the following points should be taken into consideration :
•
Avoid dusty environments
•
Check that the floor is level and capable of withstanding the weight of the STS
•
Avoid cramped environments that could impede the normal maintenance activities
•
The relative humidity should not exceed 90%, non-condensing.
•
Check that the ambient temperature, with the STS running, remains between 0 and 40 C
•
Avoid installing the equipment in places exposed to the direct sunlight and hot air.
REMOVING THE STS FROM PALLET
The STS is packed and enclosed in a structural cardboard carton to protect it from damage.
1.
Inspect for damage that may have occurred during the shipment If any damage is noted, call the shipper
immediately and retain the shipping carton and the STS.
2.
Carefully open the carton and take the STS out.
Retain the carton and packing material for possible future use
Содержание InfoSTS
Страница 45: ...44 Figure 28...
Страница 47: ...NOTES...