4.1
Handling
4.2
Environment
•
The inverter should be installed in an ade-
quately-ventilated, steel enclosure.
•
The inverter is designed to operate at full
rating at an altitude not above 1000m
(3280 ft). Derate if installed above this.
Install the inverter in a location that meets the
following requirements:
•
Ambient temperature between -10oC and
+50oC (+14oF to +122oF).
•
If the ambient maximum temperature
exceeds 40oC (104oF), remove the venti-
lation covers located one on either side to
allow increased air flow.
For other operating environment specifica-
tions, refer to Section 3.4, page 5.
4.3
Position and Materials
•
Position the inverter vertically so that the
inscriptions on the keypad panel are the
right way up.
•
Bolt the inverter firmly to a rigid structure.
•
The material of the mounting panel should
be able to tolerate the temperature attain-
able by the inverter heatsink, normally
90oC (194oF).
•
The fixing bolts should be used with nuts
or washers that will resist vibration.
•
Do not overtighten the fixing bolts.
4.4
Cooling and Ventilation
For inverter heat losses refer to page 64.
Observe the minimum clearances shown in the
illustration below.
The inverter should be installed in an enclo-
sure. The minimum clearances to adjacent
equipment must be allowed.
If two or more inverters are to be installed in
6
4 Mechanical Installation
CAUTION
Hold and lift the inverter by the
chassis/heatsink, not by the cover. The
cover is a protective shield only, and is not
intended for lifting and carrying. Lifting
the inverter by the cover or other front
parts may result in damage.
50
Minimum clearances (mm) from the
inverter to any other equipment.
120
120
50
50
50mm
minimum
between
inverters
Inverter(s) mounted on
deflector plate to nullify
the effect of other heat
source(s).
Ventilation should take
account of all other
heat-producing
equipment.
Ventilation should take
account of all other
heat-producing
equipment.
Inverter