![IMO Precision Controls Jaguar VXS Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/imo-precision-controls/jaguar-vxs/jaguar-vxs_user-manual_2048178051.webp)
49
Is power
supply voltage
within spec.
?
Overvoltage trip OU1, OU2, OU3
YES
NO
NO
Reduce
the supply
voltage
Malfunction
of inverter
— possibly noise.
Consult IMO
Braking system
malfunction.
Consult IMO
OU trip
operates if load
suddenly removed
?
YES
NO
Use AC inductors
in the motor
supply cables.
Is
DC bus voltage
≥
trip level
?
YES
NO
Does OU trip
occur when
decelerating
?
YES
NO
Can
increase decel.
time
?
YES
Reduce
load
inertia
NO
Can
load inertia be
reduced
?
YES
NO
Is
dynamic braking
in use
?
YES
Raise set point
of Function
07 or 64
Use a dynamic
braking resistor
OU1, OU2 or OU3 trip
during accel., decel., or
steady state
Are
line voltage
transients present
?
YES
NO
Rectify source of
transient overvoltages.
Consult IMO
?
STATUS
QUERY
ACTION
For VXS20-1 inverters, please refer
to IMO Precision Controls Ltd.
NOTE
Because supply inter-
ruptions can be of very
short duration, an oscil-
loscope or other dedi-
cated equipment may be
required to detect mains
dip or loss.
WARNING
If the power supply is automatically
restored after a failure, the inverter may
reset and restart automatically. Refer
to Function 14.
Содержание Jaguar VXS