61
10.3
Three-phase RFI-FP Filter
A Jaguar VXS inverter may be mounted on
the face of the Flatpack Filter using the inte-
gral tapped mounting points. Alternatively,
the filter may be mounted upright beside the
inverter.
Refer to the diagram on page 59 for details of
connections and screening.
Earth Leakage Current
Under normal running conditions, with three
phases energised, the effective leakage is
0.5mA nominal at 50Hz. At power-on, how-
ever, or if one phase fails, the leakage current
may be up 40mA.
LINE
LOAD
Single Phase
RFI Filter
H
W Y
X
L
2 earthing studs M4
L1
L1
LINE
LOAD
(PE)
(PE)
Inverter fixings, 4 holes tapped Z
L2
L2
L3
L3
(PE)
(PE)
(PE)
(PE)
WARNING The RF filter must be earth-
ed in accordance with the appropriate
circuit diagram on page 59.
Part
Jaguar VXS
Rated
Dimensions (mm)
Weight
number
inverter range
current
L
W
H
X
Y
Z
kg
at 40oC
RFI 75-3
VXS40-3 to VXS75-3
10A
195
148
40
185
90
M5
0.95
RFI 400-3 VXS150-3 to VXS400-3
25A
195
207
40
183
142
M5
1.35