13
Restart attempts
0 to 10
—
1
0
14
Restart mode
0 = Inactive; no restart
—
—
0
LU indication on V loss
1 = Inactive; no restart
LU indication on I/P voltage recovery
2 = Active; restart at same O/P frequency
as when trip occurred.
3 = Active; restart at 0Hz
15
Electronic thermal
(Motor 1)
—
—
2
overload 1 — mode
0 = Inactive
(for Electronic thermal o/l 2 1 or 3 = Active (standard 4-pole motors)
see F66/67)
2 or 4 = Active (inverter-rated motors)
16
Electronic thermal
(Motor 1) 0.01 to 99.9
0.01 to 9.99
A
0.01
*
overload 1 — level
10.0 to 99.9
0.1
0.01 to 99.9 = 20% to 105% of inverter rated current
* Default factory-set at rated current for a 4-pole standard motor for each inverter frame size.
17
DC injection braking
0 = Inactive
—
—
0
— mode
1 = Active
18
DC injection braking
0 to 60
Hz
1
0
— starting frequency
NOTE 0 = 0.2Hz
19
DC injection braking
0 to 100
%
1
50
— level
Percent of inverter rated current
20
DC injection braking
0 to 30
0.00 to 9.99
s
0.01
0.5
— time
10.0 to 30
0.1
21
Preset speed 1
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
22
Preset speed 2
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
23
Preset speed 3
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
24
Preset speed 4
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
25
Preset speed 5
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
26
Preset speed 6
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
27
Preset speed 7
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
28
S-ramp accel./decel.
0 = Inactive; linear accel. and decel.
—
—
0
— selector
1 = Active; quick S-ramp
2 = Active; slow S-ramp
Function
Setting Range
Unit Resol. Def.
No.
Name
Functions in
can be adjusted while the inverter is running. Data in […] applies to three phase inverters.
Resol. = resolution; Def. = Factory-set default — refer to Function 39.
22