Functions in
can be adjusted while the inverter is running. Data in […] applies to three phase inverters.
Resol. = resolution; Def. = Factory-set defaults — refer to Function 39.
21
00
Data protection
0 = No protection
—
—
0
(See also Function 57)
1 = Data protected (read only)
01
Input frequency reference
0 = Keypad mode,
∧
and
∨
keys
—
—
0
— mode
1 = Terminal mode, 12/C1-11
2 = Motorised pot.
refer to diagrams, p.26
3 = Motorised pot.
02
Control mode
0 = Keypad mode, RUN, STOP
—
—
0
1 = Terminal mode, P24-FWD/REV
03
Max. output frequency
50 to 400
Hz
1
50
04
Base frequency 1
(Motor 1) 15 to 400
Hz
1
60
(for Base freq. 2 see F62)
05
Max. output voltage
0 = V
∝
f (V
≤
V
L
max.)
V
1
230
0, 80 to 240 [0, 160 to 480]
[2]
[400]
— selectable V ‘shelving’
06
Acceleration time 1
0 to 3600
0.00 to 9.99
s
0.01
6.00
07
Deceleration time 1
0 to 3600
10.0 to 99.9
s
0.1
6.00
100 to 999
1
(for Acc,/Dec. 2 see F63/64)
1000 to 3600
10
08
Torque boost 1
0 = Automatic torque boost
—
1
0
1 = Squared characteristic (for pumps
and fans)
2 = Proportional characteristic
3 = Low linear boost…
…increasing in unit steps to…
(for Torque boost 2 see F65) 31 = High linear boost
09
FMA voltage
0 = 6.5V approx.
—
1
85
…increasing in units steps to…
99 = 10.5V approx.
10
Motor poles
2 = 2-pole
—
2
4
…increasing in steps of 2 to…
12 = 12-pole
Example: When a 4-pole motor is
running at 50Hz, display will read:
120 x 50 ÷ 4 = 1500rpm
11
Line speed coefficient
0 to 200
0.01 to 9.99
—
0.01
0.01
10.0 to 200.0
0.1
Example: Display value in m/min =
O/P freq. (Hz) x coefficient
12
PWM carrier frequency
0 = 0.75kHz
kHz
1
5
1 = 1kHz, to 15 = 15.6kHz
7 Inverter Functions
7.1
Functions Data
Function
Setting Range
Unit Resol. Def.
No.
Name