Function
Setting Range
Unit Resol. Def.
No.
Name
Functions in
can be adjusted while the inverter is running. Data in […] applies to three phase inverters.
Resol. = resolution; Def. = Factory-set defaults — refer to Function 39.
23
29
Protection history
Last 4 protection trips, last trip first
—
—
—
30
Starting frequency
0 to 15
Hz
1
1
NOTE 0 = 0.2Hz
31
Torque limit
0 = No limit
%
1
0
— accel./decel.
20 to 180 = Limit active
32
Torque limit
0 = No limit
%
1
0
— constant speed
20 to 180 = Limit active
33
Braking torque
0 = Low (when no dynamic brake resistor) —
—
0
— selector
1 = High (with dynamic brake resistor)
34
Bias frequency
-400 to +400
Hz
1
0
35
Input frequency reference
0 to 250
0.00 to 9.99
%
0.01 100.0
— gain
10.0 to 250.0
0.1
36
Frequency limiter — high
0 to 400
Hz
1
70
37
Frequency limiter — low
0 to 400
Hz
1
0
38
O/P current stability
0 to 10
—
1
5
39
Data initialisation
0 = Hold custom settings
—
—
0
1 = Reinstate factory-set default values
40
Terminals FMA/FMP
0 = FMA output (analog signal)
—
—
0
— selector
1 = FMP output (digital pulse signal)
41
Terminal FMA
0 = Output frequency
—
—
0
— function
1 = Output current
2 = Output torque
3 = Load factor
42
Terminal FMP
10 to 100
—
1
24
— pulse rate multiplier
43
Terminal X4
0 = Command I/P for accel./decel. 2
—
—
0
— functions
1 = Fourth I/P allowing 15 Preset speeds
2 = Command I/P for base freq. 2
3 = ‘Hold’ signal (latch for 3-wire I/P)
44
Preset speed 8
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
45
Preset speed 9
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
46
Preset speed 10
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
47
Preset speed 11
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
48
Preset speed 12
0 to 400
0.00 to 99.99
Hz
0.01
0.00
100 to 400
0.1
Preset Speeds 13, 14, 15 overleaf