![IMO Precision Controls Jaguar VXS Скачать руководство пользователя страница 9](http://html1.mh-extra.com/html/imo-precision-controls/jaguar-vxs/jaguar-vxs_user-manual_2048178009.webp)
the same enclosure, they should ideally be
side by side at a minimum spacing of 50mm.
If an inverter is to be mounted above heat-pro-
ducing equipment of any type, precautions
must be taken to ensure that the heat generated
by the lower unit does not affect the upper. A
deflector plate may be fitted below the invert-
er to nullify the heating effect, as illustrated
on the previous page.
4.5
Removable Covers and Keypad
Front cover
It is not necessary to remove the inverter front
cover for cooling. It should be left in place,
except when wiring up, for safety.
Removable side covers
Removable covers are fitted to the sides of the
inverter. Normally these should be left in
place. If the ambient temperature of the
installation is likely to exceed 40oC, these
covers should be removed.
The temperature within an enclosure should
not exceed 50oC under any circumstances.
Removable keypad
The keypad can be detached from the front
cover and mounted remotely (max. distance
5m).
Two keypad retaining screws can be released
from the back when the front cover is
removed.
A 2m screened connector cable with fitted ter-
minations is available.
7
VXS20-1 (Single Phase)
PANEL
CONTROL
PRG MODE
RUN
Hz
A
V
r/min
m/min
PRG
RESET
RUN
FUNC
DATA
STOP
*Centrelines of 3 cable entry holes, 18mm dia.
22.5
22.5
93
105
5
6
6
6
6
138
150
5
80
45.5
*
*
*
*
Removable
side-cover
17
Dimensions in mm
2 holes, 5mm
4.6
Dimensions