55
Put a flare nut slightly into the pipe and modify the flare.
Outer diameter
[D(mm)]
Depth [A (mm)]
Flaring Size [B
(mm)]
ø 6.35
1.3
8.7~9.1
ø 9.52
1.8
12.8~13.2
ø 12.70
2.0
16.2~16.6
ø 15.88
2.2
19.3~19.7
ø 19.05
2.2
23.6~24.0
Check that you flared the pipe correctly. The below figures show some examples of incorrectly flared pipes.
Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench,
applying the following torque:
Excessive torque can be the cause of gas leakage.
You must purge with oxygen-free nitrogen while brazing.
Outer diameter
[mm(inch)]
Torque (N•m)
ø 6.35
14~18
ø 9.52
34~42
ø 12.70
49~61
ø 15.88
68~82
ø 19.05
100~120