61
CHARGING REFRIGERANT
This product contains fluorinated greenhouse gases. Do not vent gases into the atmosphere.
Inform the user if the system contains 5 tCO2e or more fluorinated greenhouse gases. In this case, it must be
checked for leakage at least once every 12 months, according to regulation No. 517/2014. This activity must be
covered by qualified personnel only. In the case of the situation above, the installer (or authorized person with
responsibility for the final check) must provide a maintenance book, with all the information recorded, according
to REGULATION (EU) No. 517/2014 OF THE EUROPEAN PARLIAMENT AND OF THE COUNCIL of 16 April 2014 on
fluorinated greenhouse gases.
Please fill in the following indelible ink on the refrigerant charge label supplied with this product on and on this manual.
①
The factory refrigerant charge of the product.
②
The additional refrigerant amount charged in the field.
①
+
②
The total refrigerant charge.
a. Factory refrigerant charge of the product: See unit name
plate.
b. Additional refrigerant amount charged in the field.
(Refer to the above information for the quantity of
refrigerant replenishment.)
c. Total refrigerant charge.
d. Refrigerant cylinder and manifold for charging.
UNIT
Kg
tCO
2
e
①
,a
②
, b
①
+
②
,c
Refrigerant type
GWP
R-410A
2088
❋
GWP: Global Warming Potential
❋
Calculating tCO2e: kg x GWP/1000
Before charging, check whether the refrigerant cylinder has a siphon attached or not, and position the cylinder
accordingly.
Содержание Inuit 6I
Страница 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Страница 16: ...16 IGLU Inuit 6WTI indoor unit...
Страница 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Страница 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Страница 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Страница 20: ...20 IGLU Inuit 12WTI IGLU Inuit 16WTI outdoor unit IGLU Inuit 12WTI IGLU Inuit 16WTI indoor unit...
Страница 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Страница 31: ...31 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 32: ...32 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 43: ...43...