background image

64

 

 

CHECKING CORRECT GROUNDING 

 

If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an 

A grounding electrode must be installed. The corresponding accessories are not supplied with the Air to Water Heat 

pump. 

 
1.  Select a grounding electrode that complies with the specifications given in the illustration. 

 

 

2.  Connect the flexible hose to the flexible hose port. 

 

 

In damp hard soil rather than loose sandy or gravel soil that has a higher grounding resistance. 

 

Away from underground structures or facilities, such as gas pipes, water pipes, telephone lines, and underground 
cables. 

 

At least two meters away from a lightning conductor grounding electrode and its cable.

 

 

 The grounding wire for the telephone line cannot be used to ground the Air to Water Heat pump. 
 

 

 

 

3.  Finish wrapping insulating tape around the rest of the pipes leading to the outdoor unit. 
 
4.  Install a green/yellow colored grounding wire: 
 

 

If the grounding wire is too short, connect an extension lead, mechanically and wrap it with insulating tape. 

 

(Do not bury the connection). 

 

Secure the grounding wire in position with staples.

 

 

  If the grounding electrode is installed in an area of heavy traffic, its wire must be connected securely. 
 

 

 

 

5.  Carefully check the installation by measuring the grounding resistance with a ground resistance tester. If the resistance 

is above the required level, drive the electrode deeper into the ground or increase the number of grounding electrodes. 
 

6.   Connect the grounding wire to the electrical component box inside the outdoor unit. 
 

 

Содержание Inuit 6I

Страница 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...

Страница 2: ...REPARATION OF FIRE EXTINGUISHER 24 IGNITION SOURCES FREE 24 AREA VENTILATION 24 LEAKAGE DETECTION METHODS 25 LABELLING 25 RECOVERY 25 INSTALING THE UNIT 25 MOVING THE OUTDOOR UNIT BY WIRE ROPE 26 SPAC...

Страница 3: ...HE REFRIGERANT PIPE 56 INSULATING THE REFRIGERANT PIPE 57 BRAZING THE PIPE 57 REPLACEMENT OF NITROGEN GAS 57 PERFORMING THE REFRIGERANT GAS LEAK TEST 58 VACUUM DRYING 59 SELECTING AN ADDITIONAL REFRIG...

Страница 4: ...n health from uncontrolled waste disposal please separate these items from other types of waste and recycle them responsibly to promote the sustainable reuse of material resources Household users shou...

Страница 5: ...g to its technical parameters LIABILITY The manufacturer shall not be liable for damage caused by improper use or installation of the heat pump The manufacturer s liability shall also not apply if wor...

Страница 6: ...ize something bad such as loud noise or smell of burning To prevent electric shocks fires or injuries always stop the unit and disable the protection switch and contact IGLU TECH s technical support i...

Страница 7: ...ensed water runs well out of the unit at low ambient temperature Drainpipe and Cond heater can frost ice cannot grow If drain work is not effective for releasing condensed water it can make the units...

Страница 8: ...IFICATION PRODUCT LINE UP MODEL NAME MODEL REMARKS IGLU Inuit 6I Without water tank IGLU Inuit 6WTI With water tank IGLU Inuit 9I Without water tank IGLU Inuit 9WTI With water tank IGLU Inuit 12I With...

Страница 9: ...9 MODEL NAME MODEL REMARKS IGLU Inuit 12WTI With water tank IGLU Inuit 16I Without water tank IGLU Inuit 16WTI With water tank...

Страница 10: ...ver to the customer after finishing the installation The quantities are indicated in parentheses The base heater inside the outdoor unit works in accordance with the weather outdoors IGLU Inuit 6I IGL...

Страница 11: ...eight x width x depth mm 638x810x310 998x940x330 1420x940x330 Weight without packaging kg 46 5 72 109 Power network connection values Electrical connections 1F 220 240V 50Hz 3F 400V 50Hz Compressor ra...

Страница 12: ...h x depth mm 638x810x310 998x940x330 1420x940x330 Weight without packaging kg 46 5 72 109 Power network connection values Electrical connections 1F 220 240V 50Hz 3F 400V 50Hz Compressor rated power He...

Страница 13: ...6 2 9 67 2 18 9 40 234 8 95 2 63 8 46 2 78 7 96 2 93 5 11 2 16 4 84 2 40 7 9 72 1 55 9 45 1 66 9 00 1 87 8 80 2 10 8 60 2 33 5 10 1 66 4 80 1 81 10 10 62 1 57 10 32 1 68 9 83 1 89 9 64 2 12 9 44 2 36...

Страница 14: ...37 11 57 4 90 11 08 5 37 10 60 5 84 9 41 6 54 9 54 7 26 2 13 65 3 59 13 28 3 84 12 64 4 29 12 45 4 52 12 29 4 76 10 91 5 33 11 05 5 93 7 16 24 3 62 15 79 3 86 16 00 3 76 14 37 4 67 15 30 4 54 13 49 5...

Страница 15: ...15 MAIN COMPONENTS DIMENSIONS IGLU Inuit 6I outdoor unit IGLU Inuit 6I indoor unit IGLU Inuit 6WTI outdoor unit IGLU Inuit 6I outdoor unit IGLU Inuit 6I outdoor unit...

Страница 16: ...16 IGLU Inuit 6WTI indoor unit...

Страница 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...

Страница 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...

Страница 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...

Страница 20: ...20 IGLU Inuit 12WTI IGLU Inuit 16WTI outdoor unit IGLU Inuit 12WTI IGLU Inuit 16WTI indoor unit...

Страница 21: ...ucture such as a building that can block the sea breeze Even when it is inevitable to install the product on the seashore make sure that product is not directly exposed to sea breeze by installing a p...

Страница 22: ...usually caused by poor water quality in the heating system or by the presence of air in the system The presence of air in the system produces corrosive products such as magnetite or sediment Magnetite...

Страница 23: ...laws and regulations Do not work in a confined place The work area shall be blocked The refrigerant piping shall be installed in a position where there are no substances that may result in corrosion T...

Страница 24: ...hould be checked to ensure that there are no flammable hazards or ignition risks The No Smoking sign shall be attached Under no circumstances shall potential sources of ignition be used while in the d...

Страница 25: ...ll operate normally Hoses shall be equipped with leak free disconnect couplings Before starting the recovery check for the status of the recovery system and sealing state Consult with the manufacturer...

Страница 26: ...unit is installed In this case leaking water can be drained Do not use extra platforms for indoor units MOVING THE OUTDOOR UNIT BY WIRE ROPE Fasten the outdoor unit with two 8 m or longer wire ropes...

Страница 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...

Страница 28: ...installed according to distances declared to permit accessibility from each side either to guarantee the correct operation of maintenance or repair products The unit s parts must be reachable and rem...

Страница 29: ...29 SPACE REQUIREMENTS FOR INDOOR UNIT WHEN INSTALLING ONE INDOOR UNIT WITH WATER TANK IGLU Inuit 6WTI IGLU Inuit 9WTI IGLU Inuit 12WTI IGLU Inuit 16WTI...

Страница 30: ...30 WHEN INSTALLING MORE THAN ONE INDOOR UNIT WITH WATER TANK IGLU Inuit 6WTI IGLU Inuit 9WTI IGLU Inuit 12WTI IGLU Inuit 16WTI...

Страница 31: ...31 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...

Страница 32: ...32 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...

Страница 33: ...ix the outdoor unit with anchor bolts The anchor bolt must be 20 mm or higher from the base surface IGLU Inuit 6I IGLU Inuit 6WTI IGLU Inuit 9I IGLU Inuit 9WTI IGLU Inuit 12I IGLU Inuit 12WTI IGLU Inu...

Страница 34: ...he rack and outdoor unit Install the rack as close to the column as possible Install proper grommet to reduce noise and residual vibration transferred by the outdoor unit towards a wall When installin...

Страница 35: ...drainage out of the unit Additional drain works are required Follow the description below Make space more than 100mm between the bottom of the outdoor unit and the ground for the installation of the...

Страница 36: ...ou install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit to prevent the invasion of water from the lower direction 4 When installing the unit in a pl...

Страница 37: ...alling the product make sure that the rack is not placed under the drain hole Ensure that the drained water runs off correctly and safely In areas with heavy snowfall piled snow could block the air in...

Страница 38: ...fall areas it is very important to select an installation site where the snow will not affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is not affected by the sno...

Страница 39: ...E OF INDOOR UNIT IGLU Inuit 6WTI IGLU Inuit 9WTI IGLU Inuit 12WTI IGLU Inuit 16WTI A Refrigerant line outlet B Refrigerant line inlet C Cold water in outlet D Hot water out inlet E Heating return outl...

Страница 40: ...LU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I A Refrigerant line outlet B Refrigerant line inlet C Heating return outlet D Heating supply inlet E Heating supply for an external water tank ou...

Страница 41: ...S IGLU Inuit 6I IGLU Inuit 6WTI IGLU Inuit 9I IGLU Inuit 9WTI IGLU Inuit 12I IGLU Inuit 12WTI IGLU Inuit 16I IGLU Inuit 16WTI Make sure to install the circuit breaker with the over current and electri...

Страница 42: ...ment 18 DI COM 19 Flow of thermoficate 20 DI COM 21 0 10 Mixing valve 22 AO COM 23 RS485 24 RS485 25 RS485 GND 26 Internal heating loop pump N 27 Internal heating loop pump L3 28 Cooling valve PE 29 C...

Страница 43: ...43...

Страница 44: ...bility of the installer or the user of the equipment to ensure by consultation with a distribution network operator if necessary that the equipment is connected only to a supply with a short circuit p...

Страница 45: ...45 IGLU Inuit 6I IGLU Inuit 6WTI IGLU Inuit 9I IGLU Inuit 9WTI IGLU Inuit 12I IGLU Inuit 12WTI IGLU Inuit 16I IGLU Inuit 16WTI...

Страница 46: ...within 2 of the supply rating If the power is greatly unbalanced it may shorten the life of the condenser If the unbalanced power is exceeded over 4 of the supply rating the indoor unit is protected...

Страница 47: ...mmended to locate the outlet in a high position Place the cords so that they are not tangled INSTALLING THE EARTH WIRE Earthing must be done by your installation specialist for your safety Use the ear...

Страница 48: ...r units refer to the installation manual After peeling off cable wires from the pre installed tube insert a contraction tube If cable wires are connected without using connecting sleeves their contact...

Страница 49: ...e of the insulation tape After tube contraction work is completed wrap it with the insulation tape to finish Three or more layers of insulation are required Make sure that the connection parts are not...

Страница 50: ...uum pump Use a vacuum pump with a check valve to prevent pump oil from flowing backward while the vacuum the pump is stopped Use the vacuum pump so that the vacuum induction is available up to 5Torr 1...

Страница 51: ...tional pumps piping and controls in the water system are in accordance with relevant local laws and regulations under the installer s responsibility IGLU shall not be held liable for any damage result...

Страница 52: ...MPONENTS IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I No Name 1 Backup heater element 2 Plate heat exchanger 3 Expansion tank 4 Three way valve 5 Water pump 6 Antenna 7 Air relief mechani...

Страница 53: ...it 12 WTI IGLU Inuit 16 WTI No Name 1 Water tank 2 Three way valve 3 Backup heater element 4 Water pump 5 Flow sensor 6 Antenna 7 Air relief mechanical valve 8 Wireless communication module 9 Expansio...

Страница 54: ...the pipe pipes shall be sealed by caps Temper grade and minimum thickness of the refrigerant pipe Outer diameter mm Minimum thickness mm Temper grade 6 35 0 7 C1220T 0 9 52 0 7 12 70 0 8 15 88 1 0 15...

Страница 55: ...d the pipe correctly The below figures show some examples of incorrectly flared pipes Align the pipes to connect them easily Tighten the flare nuts first with your hands and then with a torque wrench...

Страница 56: ...urize the appliances with a pressure higher than the maximum allowable pressure as indicated on the nameplate of the unit Never directly touch any accidental leaking refrigerant This could result in s...

Страница 57: ...refrigerant pipe joints and connections with class o material If you insulate the pipes the condensed water does not fall from the pipes and the capacity of the Air to Water Heat Pump is improved Chec...

Страница 58: ...leaks Make sure to use a recommended bubble test solution for Gas Leak Test Soap water could cause cracking of the flare nuts or lead to corrosion of flared joints You may get injured when the joint o...

Страница 59: ...ssure Use the vacuum pump with the check valve to prevent pump oil from flowing backward while the vacuum pump stopped suddenly Use the vacuum pump that can be vacuumed up to 666 6Pa 5 mmHg Close the...

Страница 60: ...t 12WTI IGLU Inuit 16I IGLU Inuit 16WTI Outdoor unit of liquid 6 35 6 35 9 52 9 52 Additional charging g 20 g m 20 g m 50 g m 50 g m Additional Charge g L1 15 20 IGLU Inuit 6I IGLU Inuit 6WTI IGLU Inu...

Страница 61: ...COUNCIL of 16 April 2014 on fluorinated greenhouse gases Please fill in the following indelible ink on the refrigerant charge label supplied with this product on and on this manual The factory refrig...

Страница 62: ...ng refrigerant 1 Press the function key for adding refrigerant in cooling mode 2 After 20 minutes of operation open the valve on the gas side 3 Open the valve for the low pressure side on the manifold...

Страница 63: ...valve stem and sealing edge can be damaged and refrigerant can leak through this damage surface If the refrigerant would leak turn the valve stem back by half and tighten the valve stem again then che...

Страница 64: ...ounding electrode and its cable The grounding wire for the telephone line cannot be used to ground the Air to Water Heat pump 3 Finish wrapping insulating tape around the rest of the pipes leading to...

Страница 65: ...w mode display 4 View Mode When the K4 switch is pressed you can see information about our system state below Number of press Display contents Display Units Segment 1 Segment 2 Segment 3 Segment 4 0 C...

Страница 66: ...ect the desired option Example 3 If you have selected desired option you can shortly press the K2 to switch to adjust the value of the Seg3 and Seg4 and change the function for the selected option Exa...

Страница 67: ...ion control Main 0 3 0 0 Disabled default Enabled 0 1 Silent mode Main 0 4 0 0 Manual Silent mode 3 dB Manual Silent mode 0 9 5 dB Manual Silent mode 0 75 7 dB Manual Silent mode 3 dB Low noise Silent...

Страница 68: ...tton 7 Close each cap of the valve Use a transfer cylinder when recovering refrigerant to be reused Using a modified refrigerant vessel may cause explosion and cause damage or personal injury Relocati...

Страница 69: ...with the manifold gauge If the pressure on the high pressure side is over 3 0 MPa 30 59 kgf cm g reduces the number of operating indoor unit to decrease the pressure below 3 0 MPa 30 59 kgf cm 5 When...

Страница 70: ...drainpipe properly insulated INSTALING THE WIRE Have you performed earthing work 3 on the outdoor unit Is a 2 core cable used Is the length of the wire in the limited range Is the wiring route correct...

Страница 71: ...ensor SHORT or OPEN Hydro Unit 162 EEPROM Error Hydro Unit 198 The error of the Terminal Block s Thermal Fuse Open Hydro Unit 201 Hydro Unit Outdoor Unit communication error Matching error Hydro Unit...

Страница 72: ...Short or open circuit error of Zone 1 water out temperature sensor Hydro Unit 900 Short or open circuit error of Zone 2 water out temperature sensor Hydro Unit 901 Water inlet PHE temperature sensor e...

Страница 73: ...__________ _______________________________________________________________________ _______________________________________________________________________ _____________________________________________...

Отзывы: