49
Using a crimping tool, compress the two points and flip them over and compress another two points in the same
location.
The compression dimension should be 8.0.
After compressing it, pull both sides of the wire to make sure it is firmly pressed.
Apply heat to the contraction tube to contract it.
Wrap it with the insulation tape twice or more and position your contraction tube in the middle of the insulation
tape.
After tube contraction work is completed, wrap it with the insulation tape to finish. Three or more layers of
insulation are required.
Make sure that the connection parts are not exposed to the outside.
Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have
the same level of withstand voltage as the power cable. (Comply with the local regulations on extensions.)
In case of extending the electric wire, please DO NOT use a round-shaped Pressing socket. Incomplete wire
connections can cause electric shock or fire.
Содержание Inuit 6I
Страница 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Страница 16: ...16 IGLU Inuit 6WTI indoor unit...
Страница 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Страница 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Страница 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Страница 20: ...20 IGLU Inuit 12WTI IGLU Inuit 16WTI outdoor unit IGLU Inuit 12WTI IGLU Inuit 16WTI indoor unit...
Страница 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Страница 31: ...31 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 32: ...32 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 43: ...43...