SELECTING AN ADDITIONAL REFRIGERANT CHARGE
The basic amount of refrigerant for outdoor units charged in the factory is:
OUTDOOR UNIT (SERIES)
FACTORY CHARGE (kg)
IGLU® Inuit 6I/ IGLU® Inuit 6WTI
1.2
IGLU® Inuit 9I/ IGLU® Inuit 9WTI
1.4
IGLU® Inuit 12I/ IGLU® Inuit 12WTI
2.98
IGLU® Inuit 16I/ IGLU® Inuit 16WTI
2.98
Charge additional refrigerant according to the total length of the pipe.
Each factory charging values are determined according to a basic pipe length of 15 m.
When extra pipe lengths are required, additional charging works must be implemented as described below.
REFRIGERANT CHARGING
Additional charging amount is determined based on liquid pipe specifications.
IGLU® Inuit 6I/
IGLU® Inuit 6WTI
IGLU® Inuit 9I/
IGLU® Inuit 9WTI
IGLU® Inuit 12I/
IGLU® Inuit 12WTI
IGLU® Inuit 16I/
IGLU® Inuit 16WTI
Outdoor unit of
liquid
ø6.35
ø6.35
ø 9.52
ø 9.52
Additional charging
(g)
20 g/m
20 g/m
50 g/m
50 g/m
Additional Charge(g) = (L1-15)*20 (IGLU® Inuit 6I/ IGLU® Inuit 6WTI, IGLU® Inuit 9I/ IGLU® Inuit 9WTI)
Additional Charge(g) = (L1-15)*50 (IGLU® Inuit 12I/ IGLU® Inuit 12WTI, IGLU® Inuit 16I/ IGLU® Inuit 16WTI)
*L1-TOTAL LENGTH OF LIQUID PIPE
EXAMPLES:
IGLU® Inuit 6I, the total length of the liquid pipe is 20m.
ø6.35=(20m-15m) x20g/m=100 g.
IGLU® Inuit 12I, the total length of the liquid pipe is 20m.
ø 9.52=(20m-15m) x50g/m=250 g.
The R-410A refrigerant is blended. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add the quantity of the
refrigerant using a scale.
CHARGING REFRIGERANT
The R-410A refrigerant is blended. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add the quantity of the
refrigerant using a scale.
Содержание Inuit 6I
Страница 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Страница 16: ...16 IGLU Inuit 6WTI indoor unit...
Страница 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Страница 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Страница 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Страница 20: ...20 IGLU Inuit 12WTI IGLU Inuit 16WTI outdoor unit IGLU Inuit 12WTI IGLU Inuit 16WTI indoor unit...
Страница 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Страница 31: ...31 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 32: ...32 WHEN INSTALLING ONE INDOOR UNIT WITHOUT WATER TANK IGLU Inuit 6I IGLU Inuit 9I IGLU Inuit 12I IGLU Inuit 16I...
Страница 43: ...43...