SmartPLC SafeLine with PROFIBUS slave interface
142
8.5
Notes on the firmware update
42293
An update of the firmware of AC412S must only be made by an authorised employee of ifm
electronic gmbh.
► Contact your AS-i specialist for more information.
After a firmware update, the user must re-evaluate the existing, safety-relevant application
and ensure that the defined safety function continues to be met correctly.
► Re-evaluate the safety-relevant application.
► Compile safety-relevant application again, load it to device and create boot application.
>
8.6
Connect and address AS-i slaves
41575
To integrate AS-i slaves into an AS-i network that is controlled by one of the AS-i masters of the
device:
1 Connect and address the AS-i slave
►
Connect ONE AS-i slave to be addressed to the requested AS-i network (AS-i 1 or AS-i 2) as described in the
corresponding installation instructions.
►
Assign the desired address to the AS-i slave
(→
Quick setup: Address the AS-i slaves connected to AS-i Master 1
) or →
Quick setup: Address
the AS-i slaves connected to AS-i Master 2
►
Optional: Repeat step 1 to connect and address further AS-i slaves.
2 Project the AS-i network
►
Carry out a projection adaptation on the AS-i master with the newly addressed AS-i slaves
(→
Quick setup: Project AS-i networks
>
The AS-i master adds the detected slaves (LDS) to the list of the projected slaves (LPS).
>
The AS-i slaves have a valid address and are integrated in the AS-i network.