SmartPLC SafeLine with PROFIBUS slave interface
35
Electronic sensors
42220
>
Device type S-1
42198
Circuit diagram/wiring diagram
Description
Safety classification
max. SIL max. PL max. cat.
Electronic sensor
Two-channel connection (4-wire
operation)
Self-testing with 2 OSSD outputs (test
signals are generated by the sensor and
filtered or ignored by AC412S
Examples (ifm art. no.):
– GI701S
– GM701S
– GM705S
3
e
4
► Note the supply voltage limits of the sensor.
► Select the input circuits according to the max. safety classification (SIL / cat. / PL).
When the indicated ifm articles are used, the maximum safety classification according to the
SIL/Cat./PL values listed in the table can be achieved. Note the current standards.
► If other than the indicated products are used, note the current standards.
► Test the safety function within the two-error occurrence time.
The second-error occurrence time takes 24 hours. Within this time the safety function of
the device should be requested once.