SmartPLC SafeLine with PROFIBUS slave interface
223
10.7.3
OSC messages: Safety module
42325
Message
Type
Corrective measures
An internal fault in the safety board was detected
<Fehlernummer1>, <Fehlernummer2>
Error
► Note the message and contact the ifm service centre.
Wrong code sequence on the safe slave AS-i
<1,2>, Slave <1,...,31>
Error
► Replace slave with slave with unambiguous code
sequence
Configured slave missing: AS-i <1,2>, slave
<1,...,31>
Error
► Connect the missing AS-i slave to the AS-i network
OR:
► Carry out projection adaptation
([Quick-Setup] > [Alles projektieren])
Cross-networking participant <Name> missing
Error
► Check cross networking
The safety board was switched to the operating
mode <Operate, Maintenance>
Event
not necessary
The safety configuration "<Name>" was loaded
Event
not necessary
The safety configuration "<Name>" was deleted
Event
not necessary
The safety configuration is not readable
Event
not necessary
The safety configuration "<Name>" was enabled
by <Kurzzeichen>
Event
not necessary
>
OSC messages: AS-i 1 / AS-i 2 (safety)
42320
Message
Type
Corrective measures
ASi_GlobalCom_FailureAscendingAddrSequ_e;
currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Note the message and contact the ifm service centre
ASi_GlobalCom_FailureMissingBusCycleEvents_e;
currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Note the message and contact the ifm service centre
At least two AS-i slaves with the same code
sequence were detected: currDev=%s;
currDiagState=%s; prevDiagState=%s; addr1=%s;
addr2=%s
Error
► Replace one of the slaves with slave with unambiguous
code sequence
The code sequence of a safe input slave is not
compliant: currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Replace slave with slave with unambiguous code
sequence
Error in code sequence during the teach process
(0x5827): currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Check configuration of the AS-i network
Error in code sequence during the teach process
(0x5820): currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Replace slave with slave with unambiguous code
sequence
Safe AS-i input slave of type positively guided
waiting for testing: currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Carry out testing for safe AS-i slave
ASi_SYS_ERROR_CFG_CANTADDSLAVE_e;
currDev=%s; currDiagState=%s;
prevDiagState=%s; addr1=%s; addr2=%s
Error
► Maximum number of the control slaves reached; check
logical interfaces of the project
>
OSC messages: CODESYS (safety)
42318