SmartPLC SafeLine with PROFIBUS slave interface
195
PROFIBUS modules: compatibility mode AC1305/06/26
41808
Slot
Description
Detailed information
1
Digital inputs and outputs of single or A slaves,
connected to AS-i master 1
→
Slots 1...4 – Digital inputs/outputs on AS-i Master 1/2
(
→ S.
2
Digital inputs and outputs of single or A slaves,
connected to AS-i master 2
(only available for devices with 2 AS-i masters)
→
Slots 1...4 – Digital inputs/outputs on AS-i Master 1/2
(
→ S.
3
Digital inputs/outputs of B slaves, connected to AS-i
master 1
→
Slots 1...4 – Digital inputs/outputs on AS-i Master 1/2
(
→ S.
4
Digital inputs/outputs of B slaves, connected to AS-i
master 2
(only available for devices with 2 AS-i masters)
→
Slots 1...4 – Digital inputs/outputs on AS-i Master 1/2
(
→ S.
5
Multiplexed analogue inputs of AS-i Master 1/2
→ Note
6
Multiplexed analogue outputs of AS-i Master 1/2
→ Note
7
Command channel (fieldbus)
→ Note
8
Data from the device-internal Standard-SPS to the
higher-level fieldbus controller
→
Slot 8 – Inputs from Standard-SPS
(
→ S.
9
Data of the higher-level fieldbus controller to the
device-internal Standard-SPS
→
Slot 9 – Outputs to AC14 Standard-SPS
(
10
Analogue inputs of up to 15 AS-i slaves on AS-i Master
1/2
→
Slot 10 – Analogue inputs on AS-i Master 1/2
(
→ S.
11
Analogue outputs of up to 15 AS-i slaves on AS-i
Master 1/2
→
Slot 11 – Analogue outputs on AS-i Master 1/2
(
→ S.
12
Command channel (host)
→ Note
The slots 5, 6, 7 and12 are not evaluated by AC412S.
Data to the higher-level PROFIBUS PLC are set to "0".
Data directed to AC412S are rejected.