SmartPLC SafeLine with PROFIBUS slave interface
75
7.3.7
Quick setup: Address the AS-i slaves connected to AS-i Master 1
41764
To change the address of an AS-i slave connected to AS-i Master 1:
1 Select the menu page
►
►
Select [Addressing AS-i 1] tab.
2 Select the AS-i slave
>
The page provides an overview of the current addressing
and status of the AS-i slaves on the selected AS-i master
(→ figure)
Notes on colour codes: →
Overview of slave states
(→ S.
►
Select the AS-i slave of which want to change the
address.
►
Use [Select] to activate the selected AS-i slave.
3 Select a new AS-i address
>
The page provides an overview of the free AS-i addresses
(→ figure)
Notes on colour codes: →
Overview of free slave
addresses
(→ S.
►
Select the address to be assigned to the AS-i slave.
►
Assign the selected address with [Select].
>
The confirmation prompt appears.
►
Confirm the message with [OK].
>
The AS-i slave has new address.
>
The page provides an overview of the current addressing
and configuration errors (→ figure)
4 Address additional AS-i slaves (optional)
►
Repeat steps 2 and 3 to address additional AS-i slaves.
After the address change, the present configuration no longer corresponds to the stored
configuration.
>
The slave status indicates a configuration error.
To eliminate the configuration error:
► Start a projection adaptation (→
Quick setup: Project AS-i networks
(