IEI MiniMax 3 Installation/Programming Manual Section 3: Programming
3.11 Programming the Door Ajar Output Time
To program the Door Ajar Output time use command 44. You can program it from 10 to 990 seconds in 10 second increments. The
default value is 30 seconds, which means the output triggers if the door position switch is held open for 30 seconds. The command
sequence is as follows:
Action
Command
Enter Program Mode
99 # master code *
Delete Users
44 # time # 0 # ** (10 to 990 Seconds)
Exit Program Mode
*
3.12 Programming the Forced Door Time
To program the Forced Door output time use command 45. You can program it from 10 to 990 seconds in 10 second increments. The
default value is 10 seconds, which means the output triggers immediately after 10 seconds. The command sequence is as follows:
Action
Command
Enter Program Mode
99 # master code *
Delete Users
45 # time # 0 # ** (10 to 990 Seconds)
Exit Program Mode
*