Section   2:   Installation                                                                   IEI   MiniMax   3   Installation/Programming   Manual

2.10  Wire the Alarm Shunt Relay

The Alarm Shunt Relay is used when you are controlling access to a door that is monitored by an external alarm system. This relay 
activates at the same time as the Main Relay (by either a valid code/card or REX) so you can bypass the existing alarm panel, as 
shown in the diagram below. For this feature you must wire dedicated door contact to terminals TS6 (door contact switch input) as 
shown below. The Alarm Shunt Relay remains energized until one second after the door contact switch input is closed. Remember you 
must 

remove jumper JP1

 for the door contact input to operate.

Page 18 of 48                                                                                                                 Document #: 6055672, Rev 1.0 D1c

Figure 12: Wiring the Alarm Shunt Relay

Содержание MiniMax 3

Страница 1: ...IEI MiniMax 3 Installation Programming Manual Document Number 6055672 Revision 1 0 Date 01 23 07...

Страница 2: ...Door Ajar Relay 19 2 12 Wire the Forced Door Relay 20 2 13 Network the MiniMax 3 21 2 13 1 Connect the MiniMax 3 Backplane Directly to a PC 21 2 13 2 Connect Multiple Backplanes Together 22 2 13 3 Con...

Страница 3: ...14 Programming Error Lockout 39 3 14 1 Setting the Error Lockout Threshold 39 3 14 2 Setting the Error Lockout Duration 39 3 15 Programming Wiegand LED Active State 39 3 16 Programming Wiegand Sounder...

Страница 4: ...3 Figure 6 Connecting Diode Across Maglock 13 Figure 7 Connecting MOV Across Strike 13 Figure 8 Connect Secured Series Front End to DCM 14 Figure 9 Connect Primary Wiegand Front End Reader to DCM 15 F...

Страница 5: ...er USB to RS485 Converter or LAN connection using SEG M or SEG 1 Audit Trail 2000 Event Transaction Log Front End Support Each Max 3 Module supports either two Wiegand or Secured Series front End read...

Страница 6: ...Cable Stranded wire with overall foil shield Mechanical Enclosure Surface mount Height 3 56 9 04cm Width 11 29 28 67 cm Length 11 31 28 7 cm Material 19 gauge steel Environmental Temperature Toleranc...

Страница 7: ...cifications 1 4 Max 3 Door Control Module Diagram The diagram below shows the component locations and terminal connections on the Max 3 Door Control Module Document 6055672 Rev 1 0 D1c Page 7 of 48 Fi...

Страница 8: ...ions on the Backplane Notes The Max 3 communicates to the PC via an RS 485 connection For this connection use TS3 on the far right bottom of the backplane The module is then connected to the backplane...

Страница 9: ...mounted to Max 3 Module 1 Secured Series Software Package 1 MiniMax 3 Installation and Programming Manual Please check the contents of the enclosure and verify all components on the packing list are p...

Страница 10: ...ly grounding the unit before making any connections or even touching the backplane the large circuit board in the enclosure Wire as shown and plug the transformer into a grounded electrical socket Pag...

Страница 11: ...e backplane This cable is connected from P5 on the upper right corner of the module to the three position connector underneath the module on the top right of the backplane labeled P1 Simply plug one e...

Страница 12: ...ive side to negative on your power supply When using an Electric Strike connect the lock s positive side to the normally open NO terminal and the negative side to negative on your power supply Connect...

Страница 13: ...You must connect the diode as close as possible to the locking device for it to work properly 2 5 2 Installing an MOV to Prevent Electrical Kickback from Lock AC Locks Only If your electric locking de...

Страница 14: ...on the Max 3 Backplane There is a fast tab located under each module on the lower edge of the backplane They are labeled FT1 FT2 FT3 and FT4 Connect the drain wire from the front ends connected to mod...

Страница 15: ...ire inside the foil shield from the front end cable to the fast tab located on the Max 3 Backplane There is a fast tab located under each module on the lower edge of the backplane They are labeled FT1...

Страница 16: ...front end cable to the fast tab located on the Max 3 Backplane There is a fast tab located under each module on the lower edge of the backplane They are labeled FT1 FT2 FT3 and FT4 Connect the drain w...

Страница 17: ...rs to the feature that automatically locks the door one second after the door contact switch is opened This allows you to program a long unlock time when required without worrying about the door remai...

Страница 18: ...either a valid code card or REX so you can bypass the existing alarm panel as shown in the diagram below For this feature you must wire dedicated door contact to terminals TS6 door contact switch inp...

Страница 19: ...command 44 the relay energizes and remains energized until the door contacts are closed Remember you must remove jumper JP1 for the door contact input to operate The diagram below shows how switch po...

Страница 20: ...remains energized until either a valid code is entered or card presented to the Front End Reader a valid code is entered on the Max 3 Module or the Forced Time command 45 expires The diagram below sh...

Страница 21: ...ired in parallel which means if one unit goes off line the rest are unaffected and increased data transfer speed To make this connection connect the Data A Data B and GND terminals on TS3 See below to...

Страница 22: ...multiple backplanes remember that each backplane can be up to 4000 feet away from the converter For example if your PC was centrally located with two units in either direction at 4000 feet the two ba...

Страница 23: ...wire harness from J1 on the SEG M to P5 on the module and P1 on the backplane To connect additional backplanes to the system simply connect TS3 on the first backplane to TS3 on the next backplane as...

Страница 24: ...e supplied 3 conductor wire harness from P5 to the RS 485 connector underneath the module on the backplane P1 To connect additional backplanes to the system simply connect TS3 on the first backplane t...

Страница 25: ...itch must be wired to an alarm panel or other device that sounds an alarm and or prevents anyone from gaining access through the protected door IEI recommends using a Sentrol 3012 tamper switch not pr...

Страница 26: ...terminals marked AC and EGND Provided with the Max 3 are Backup Battery Connection Cables Connect these cables from your 12V battery 7AH Recommended to the Backplane at the terminals marked B and B Po...

Страница 27: ...C Power is present LED 3 should be lit This indicates that DC Power is available on the Backplane On the Max 3 Module LED 1 should be lit This indicates that the Max 3 Module is receiving power and fu...

Страница 28: ...program the Max 3 Door Control Module You can either program it using the detachable keypad or you can program it using the PC software Using the PC software gives you access to many more features th...

Страница 29: ...cuit board Momentarily pushing this button forces the unit into program mode You then should change the master code immediately 3 2 2 Changing the Master Code The master code is stored in user memory...

Страница 30: ...to reprogram this time This time affects standard unlock users type 1 If you need to program the Main Relay to toggle you must program a toggle user See the user section for details on user types Acti...

Страница 31: ...te period of time Entering the same or another toggle code re locks the unit Standard Access 1 Normal access users are the default user type This user type unlocks the door for the duration of the Mai...

Страница 32: ...s follows Action Command Enter Program Mode 99 master code Program User 50 user type user location present card Exit Program Mode 3 6 4 Programming 26 Bit Card Only Users without Presentation To progr...

Страница 33: ...combination Refer to table4 for details on user types The programming sequence is as follows Action Command Enter Program Mode 99 master code Program User 52 user type user location code repeat code...

Страница 34: ...cannot be programmed as a Card Only user The card loading stops automatically once the current user location exceeds 2000 Pressing any key on the faceplate aborts the loading process Action Command E...

Страница 35: ...can delete a block of consecutive users using command 58 This command requires you enter the starting user location you want the deletion to begin and how many users from that point you want to delete...

Страница 36: ...e 3 10 Programming User Lockout User lockout is used to lock down the controller so users cannot gain entrance through the door If a locked out user attempts to gain access after a lockout code user t...

Страница 37: ...uence is as follows Action Command Enter Program Mode 99 master code Delete Users 44 time 0 10 to 990 Seconds Exit Program Mode 3 12 Programming the Forced Door Time To program the Forced Door output...

Страница 38: ...imezones Action Command Enter Program Mode 99 master code Enable Timezones 30 9 1 Disable Timezones 30 9 0 Exit Program Mode 3 13 2 Enable Disable Auto Unlock Use the following command to enable or di...

Страница 39: ...gram Mode 3 14 2 Setting the Error Lockout Duration To set the error lockout duration use the following command The default is 10 seconds Action Command Enter Program Mode 99 master code Program Error...

Страница 40: ...1 Exit Program Mode 3 17 Enable Disable Control Module Audio Indicators Control Module audio indicators refers the the sounds generated by the controller to indicate various conditions after a code is...

Страница 41: ...g Action Command Enter Program Mode 99 master code Reset System Defaults 40 00000 00000 Exit Program Mode 3 18 2 Erasing Entire Memory Resetting System Defaults Entering command 46 deletes everything...

Страница 42: ...gram Mode 3 19 2 Selecting Daylight Savings Time Format Below is the command to select which Daylight Savings Time format you wish to use United States US or European Below the command is a chart cont...

Страница 43: ...Enabled 5 User Lockout Enable 0 Disabled 1 Enabled 9 Time Zone Select 0 Disabled 1 Enabled 11 Auto Unlock Select 0 Disabled 1 Enabled 12 First In Auto Unlock 0 Disabled 1 Enabled 13 Daylight Savings T...

Страница 44: ...e repeat code present card User Types 0 Toggle 1 Standard 3 Lockout 4 Extended 5 Single Use 6 Relock 7 Emergency Program User Card Only By Presenting Card 50 user type user location present card User...

Страница 45: ...her Enable Disable Users 56 enable disable user location Enable 0 Disable 1 Program Consecutive Users Card Only Without Presenting Cards 57 number of users user location card PIN card pin Number of Us...

Страница 46: ...d is drawing too much current 2 Disconnect the Front End Reader and see if LED 4 turns on If LED 4 does not illuminate there may be a problem on your Max 3 Module 3 CALL IEI TECH SUPPORT 4 2 Keypad Se...

Страница 47: ...o replace the battery first power down the module using the On Off switch SW1 SW4 located on the backplane Then remove the battery carefully by lifting it out of the holder Replace the battery with a...

Страница 48: ...International Electronics Inc 427 Turnpike St Canton MA 02021 U S A Phone 800 343 9502 781 821 5566 Fax 781 821 4443 Website www ieib com...

Отзывы: