Analog status
The operational status of the analog input or analog output is indicated for each channel. If the status is 0, this means
the value is normal as an analog value.
■
Analog input
*1 The analog cartridge version number is printed on the side of the analog cartridge. For details, see “Checking the Version
Status
Description
Analog input
value
0
Operating normally
Current analog
input value
1
Converting data (occurs fro approximately 500 ms after the power is turned on and after the
user program is downloaded.)
Undefined value
2
Initializing
0
3 to 4
Reserved
–
5
Wiring error (out of the maximum ranger)
Maximum value
Signal type
Voltage
DC 0 to 10 V
For V100
: 10.0 V or higher
For V201
and later: 10.2 V or
higher
current
DC 4 to 20 mA
For V100
: 20.0 mA or higher
For V201
and later: 20.32 mA or
higher
DC 0 to 20 mA
For V100
: 20.0 mA or higher
For V201
and later: 20.4 mA or
higher
Thermocouple/
Resistance
thermometer (RTD)
The input maximum value or greater. The maximum value
varies by the signal type. For details, refer to Chapter 3
“Analog Input Value Linear Conversion Range When Set to
Celsius or Fahrenheit” on page 3-91.
6
Wiring error (out of the maximum ranger, open current loop)
Minimum value
Signal type
Voltage
DC 0 to 10 V
For V100
: 0 V or lower
For V201
and later: -0.2 V or
lower
current
DC 4 to 20 mA
For V100
: 4.0 mA or lower
For V201
and later: 3.68 mA or
lower
DC 0 to 20 mA
For V100
: 0 mA or lower
For V201
and later: 0 mA or
lower
Thermocouple/
Resistance
thermometer (RTD)
The input minimum value or smaller. The minimum value
varies by the signal type. For details, refer to Chapter 3
“Analog Input Value Linear Conversion Range When Set to
Celsius or Fahrenheit” on page 3-91.
7
Reserved
–
8
The setting in the ladder program/ FBD program differs from the attached analog cartridge
Undefined value
9
The analog cartridge has not been attached
Undefined value
10
The analog cartridge has been attached, but it is set to unused for the Type
Undefined value
11
Analog cartridge unsupported model (FT1A-*12RA-*) has been selected
Undefined value
12 to
65535
Reserved
–
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...