SmartAXIS Touch User's Manual
1-3
1 About the SmartAXIS
1
General Information for SmartAXIS
1.3 Special Functions for the Touch
This section describes the functions of the Touch.
●
I/O Related Functions
■
Catch Input
The catch input allows it to receive short input pulses from sensors without regard to the scan time. A maximum of
four catch inputs can be used.
■
Input Filter
The input filter can be adjusted according to the width of input signals to reject input noises. Selectable input filter
values to pass input signals are 0 millisecond, and 3 through 15 milliseconds in 1 millisecond increments.
■
Interrupt Input
The interrupt input can be used to call an interrupt program to respond to an external input that requires a response
faster than the scan time. A maximum of four interrupt inputs can be used. This can only be used when ladder
program is selected as the programming language for control function.
■
Stop and Reset Inputs
Stop input is a function to stop the ladder program or FBD program operation for the Touch. Reset input is a function
to stop the ladder program or FBD program operation for the Touch and clear the value of control devices. Any input
terminal on the Touch can be designated as a stop or reset input to control the Touch operation.
■
Analog Input
Analog input of 0 to 10V DC or 4 to 20 mA can be converted to a digital value of 0 to 1000. A maximum of two inputs
can be used as analog inputs.
■
Analog Output
Analog output converts a digital value between 0 and 1000 to analog value of 0 to 10V DC or 4 to 20 mA and outputs
it. A maximum of two outputs can be used as analog outputs.
■
Remote I/O
When the number of Touch inputs and outputs is insufficient, the number of inputs and outputs can be expanded to
a maximum of 156 points by connecting the SmartAXIS Pro/Lite as remote I/O slaves. With the remote I/O function,
the analog inputs on the SmartAXIS that are connected as remote I/O slaves can also be used.
■
Expanded Analog I/O
Expanded analog I/O allows the Touch to handle analog inputs for voltage, current, thermocouples, and Resistance
thermometer outputs for voltage and current by using analog cartridges. The Touch can be expanded to a maximum
of four analog inputs and outputs.
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...