SmartAXIS Touch User's Manual
3-65
4 Special Functions
3
Pr
oject
■
Comparison output reset
When the special internal relay turns on, the comparison output selected on
High-speed Counter Settings
turns off.
■
Reset input
When reset input is turned on, the current value returns to the reset value.
■
Preset value, reset value storage locations
The preset value and the reset value for the high-speed counter are stored in special data registers as 2 words.
When the 32-bit data storage setting in the function area settings is set to
from Lower Word
, the lower word is
stored in the first device.
■
HSC reset input and reset status
When the HSC reset input is enabled in group 1, turn on HSC reset input I2 to return the current value to the reset
value.
In this situation, reset status turns on for only one scan.
To use the reset input with group 1 single-phase high-speed counter, use I2 (group 2). When not using I2 as a reset
input, it can be used as normal input, high-speed counters, catch input, interrupt input, or frequency measurements.
■
Count direction flag
These special internal relays maintain whether group 1 current value count is being added or subtracted.
When these special internal relays are on, they indicate addition. When they are off, they indicate subtraction.
Group
1
(I0 to I1)
2
(I2)
3
(I3)
4
(I4)
5
(I5)
Read/Write
Comparison
Output Reset
M8030
M8040
M8055
M8166
M8173
R/W
Group
1
(I0 to I1)
2
(I2)
3
(I3)
4
(I4)
5
(I5)
Read/Write
Reset Input
M8032
M8042
M8057
M8170
M8175
R/W
Reset input
N
N-1
N+1
Reset value (initial value)
Current value
Group
1
(I0 to I1)
2
(I2)
3
(I3)
4
(I4)
5
(I5)
Read/Write
Preset Value
(Upper word)
D8052
D8058
D8070
D8136
D8142
R/W
Preset Value
(Lower word)
D8053
D8059
D8071
D8137
D8143
Reset Value
(Upper word)
D8054
D8060
D8072
D8138
D8144
Reset Value
(Lower word)
D8055
D8061
D8073
D8139
D8145
Group
1
(I0 to I1)
2
(I2)
3
(I3)
4
(I4)
5
(I5)
Read/Write
HSC Reset Input
I2
–
–
–
–
–
Reset Status
M8033
–
–
–
–
R
HSC reset input
Reset status
N
N-1
N+1
Reset value (initial value)
Current value
One scan
Group
1
(I0 to I1)
2
(I2)
3
(I3)
4
(I4)
5
(I5)
Read/Write
Count Direction
Flag
M8037
–
–
–
–
R
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...