SmartAXIS Touch User’s Manual
18-5
2 Recipe Function Configuration Procedure
18
Rec
ipe
Fun
cti
on
5
Enter the name for the Recipe function in
Recipe Name
.
The maximum number is 40 characters.
6
Specify the destination device for the Recipe values in
Top Device
.
To read values of devices and save them as a recipe file, specify the source device of the values.
Click
to display the Device Address Settings dialog box.
For the device address configuration procedure, refer to Chapter 2 “5.1 Device Address Settings” on page 2-62.
The specified device addresses are configured sequentially from the number 1 in
Data List
on the
Data
tab.
7
Select the data type for the values to write with
Data Type
.
To read values of devices and save them as a recipe file, specify the type of data for the read values.
8
With
Number of Data
, specify the number of destination devices starting with the device address configured by
Top
Device
.
To read values of devices and save them as a recipe file, specify the number of source devices.
The sequential device addresses from the starting address for the number of configured devices is displayed in
Data
List
on the
Data
tab.
The amount of data that can be set varies based on the data type. When
BIN16 (+)
,
BIN16 (+/-)
, or
BCD4
is
selected for
Data Type
, up to 8,192 items of data can be configured. When
BIN32 (+)
,
BIN32 (+/-)
, or
BCD8
is
selected, up to 4,096 items of data can be configured.
9
With
Display Type
, select the display type for
Data
to configure in
Data List
on the
Data
tab.
To save data to a recipe file, the display type is decimal for all.
10
Click the
Data
tab.
The data for the recipe in the amount specified by
Number of Data
on the
Channel
tab is configured in
Data List
.
In
Device
, the devices are sequentially configured starting from the device address specified by
Top Device
.
11
Double click the data cell for each number in
Data List
to enter the value to write to the device.
The value of device that can be configured varies based on
Data Type
and
Display Type
configured on the
Channel
tab.
When
Read-only
is selected under
Trigger Setting
on the
Block
tab, entering values of devices is unnecessary.
Содержание SmartAXIS Touch FT1A Series
Страница 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Страница 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Страница 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Страница 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Страница 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Страница 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Страница 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Страница 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Страница 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Страница 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Страница 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Страница 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Страница 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Страница 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Страница 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Страница 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...