PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual | June 2017
7
2.3
Cabinet Tamper Switch
The enclosure tamper input signals to the monitoring station or remote computer that the Reader Expander
enclosure has been opened. The tamper input switch shall be mounted into the steel bracket provided and
connected to the tamper connection terminals as shown in the diagram below. The tamper input opens and
closes trouble zone RDxxx:01 on the Reader Expander.
Bracket
Tamper Switch
AC
AC
ST
TP
TP
Tamper Input Connection
2.4
Earth Ground Connection
The Reader Expander has a connection for earth ground. For best results a cold water pipe should be used with
a pipe wiring clamp. If a cold water pipe is not available, connect to a suitable ground connection in the
installation. A minimum 14AWG solid copper wire shall be used from the Reader Expander's earth connection
point to the clamp on the cold water pipe. If other earth clamps are present at the same connection point
connect the clamp below the existing units.
To other earth connecons already
aached to the earth peg or water
pipe
Cold water pipe grounding earth
peg grounding rod
AC
AC
ST
TP
TP
Main Earth Ground Connections