22
PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual | June 2017
4.3
Magnetic Reader Connection
The Protege Reader Expander allows the connection of standard magnetic track 2 format cards and provision is
made in the software for a large number of formats. Formats include BIN (Bank Identification Number) for ATM
access control, Full 16 Character decoding, and a range of first 4, 5 and 6 card number encoding.
For information on the use of magnetic readers please refer to Application Note
AN 009 Connecting Magnetic
Card Readers
available at www.incontrol.co.nz.
4.4
Door Contact Connection
The Reader Expander allows the connection of up to 4 contacts for monitoring and controlling access control
doors. Each zone on the Reader Expander can be used for the door function that is automatically assigned and
as a normal zone input on the system. The following example shows the connection of a normally closed door
position monitoring contact to monitor the open, closed, forced and alarm conditions of the door.
DOOR CONTACT
NORMALLY CLOSED
REQUEST TO EXIT
NORMALLY OPEN
+A
UX
-
Z1
COM
CO
M
Z2
Z3
Z4
Standard Door Contact Inputs
i
When connected the REX input can be programmed to operate regardless of the door contact state.
The REX input can also be programmed to recycle the door alarm time to prevent nuisance alarms
when the door is held open to permit longer entry.
UL
ULC
REX and REN devices must be listed to UL 294 for UL installations and CAN/ULC-S319 for ULC
installations, and be compatible with the system.