PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual | June 2017
23
4.5
Door Lock Connection
The Protege Reader Expander provides a connection for 2 electric strike locks with full monitoring of the lock
circuit for tamper and over current/fuse blown conditions. The door lock monitoring can be disabled if it is not
required. For information on the LOCK control status, refer to the Indication section on page .
For locking devices that have different voltage or current requirements than is available at the L1+/- or L2+/-
terminals, a FORM C relay contact is also provided, with the RELAY 1 contacts operating in parallel with L1
output and the RELAY 2 contacts operating in parallel with the L2 output.
B1+
B1-
B2+
B2-
P3
P4
+
-
1N4007 Diode
12VDC Electric
Locking Device
Door Lock Powered Outputs
+
-
1N4007 Diode
12VDC Electric
Locking Device
+
-
Power Supply for
Locking Devices
Max 30VDC
NO
CO
M
N
C
Contact Rating 7A,
30VDC or 30VAC
Door Lock Relay Outputs
i
When using a door with an entry and exit reader, the LOCK output shall be connected to LOCK 1,
and enable the swap lock option for the second reader input to allow the reader LED's to display
the correct status.
The 1N4007 diode (as shown in the above diagrams) is supplied with the Protege Reader
Expander and MUST be installed at the electric strike terminals.
UL
ULC
Class 1 wiring is required for NO relay circuit connection of 8-10A