PRT-RDE2-PCB
Protege Ethernet 2 Reader Expander
Installation Manual | June 2017
7
Configuration Switch
The addressing of the Reader Expander allows up to 128 devices to be connected to the system controller. The
'CONFIG' configuration DIP switch allows each Reader Expander to have a unique address.
7.1
Address Configuration
The switch positions 1 to 7 select the device address from 1 to 128. When setting an address the Reader
Expander must be powered down (Battery and AC) and restarted for the new address to take affect. When
changing the address the Reader Expander will automatically default the internal configuration and require a
network update. See the Protege System Reference Manual for information on performing a module update.
1
ADDRESS 1
2
ADDRESS 2
3
ADDRESS 4
4
ADDRESS 8
5
ADDRESS 16
6
ADDRESS 32
7
ADDRESS 64
8
DEFAULT/RUN
ON
OFF
Reader Expander CONFIG Switch Functions
The device address is determined by adding the value of each switch that is selected in the ON position and
then adding 1 to this value. In the example below the address 079 results in (64+8+4+2) + 1 = 079. Setting all
address switches to OFF results in the default address of 001.
1
ADDRESS 1
2
ADDRESS 2
3
ADDRESS 4
4
ADDRESS 8
5
ADDRESS 16
6
ADDRESS 32
7
ADDRESS 64
ADDRESS 079
Reader Expander Configured For Address 079