Innovative Circuit Technology Ltd.
5
•
Two clear snap on covers in insulate main dc power connections (shipped
on unit)
•
Two seven-pin alarm output, remote sensor input connector plugs
(shipped on unit)
•
This instruction Manual
To complete the installation, install GMT fuses appropriately sized for the
connected load devices.
CAUTION
Risk of personal injury or damage to equipment! Always observe the following:
•
Install unit in a restricted access location (such as an equipment rack) to limit
unintentional contact with terminals and wiring
•
Ensure the total power consumption of the loads does not exceed the 100
amperes (continuous) rated capacity of each power bus
•
Channel output fuses must not exceed 20 amperes maximum rating (16
amperes continuous)
•
Do not block air inlet or outlet openings in the panel sides
Figure 1: Back Panel Connections
Mount the Dual Bus Distribution Panel in a 19 inch equipment rack, using standard
rack mounting hardware. (Not provided)
Install appropriately rated fuse in desired channel locations by carefully inserting a
3 pin GMT fuse, where the side of the fuse that has the two pins closest is facing
upwards. Fuse only fits in one direction, do not force wrong orientation.
Bus A Outputs
and Returns
Channel 1-10
Bus B Outputs
and Returns
Channel 1-10
Site Alarm
inputs 1-5
Bus A Alarm
out
C/NC/NO
Bus B Alarm
out
C/NC/NO
LAN Port
10/100
Base-T
Bus B Return
(Common)
Bus B Input
(100A cont.)
Bus A Input
(100A cont.)
Bus A Return
(Common)