Innovative Circuit Technology Ltd.
16
Data Logging:
Data Logging rate:
Enable this feature to keep a running record the bus
voltage, bus current, channel output currents, fuse status, and alarm inputs at
a rate of up to one sample per minute. View this Comma Separated Values
(CSV) format log by clicking the
Download Log
button, and open in any
Spreadsheet software, such as Microsoft Excel. The log will store up to 30 days
of data, with the oldest entries at the top of the file, newest at the bottom.
Log Start Date
: Shows the date/time the most recent log began.
Bus Setup
Use this page to configure each bus. Select Bus A, or Bus B in the
Select a Bus to
Edit
box to call up the settings for that bus. Click on the
Save Settings
button at the
bottom of the page to save any changes.
Bus A/B Settings:
Bus Name:
Enter a descriptive name for the selected bus if desired
Bus A/B Under Voltage Alarm:
Under-Voltage Threshold:
Enter the bus under voltage value. Bus voltage
dropping below this level will trigger a Bus Under-Voltage alarm.
Under-Voltage Recovery:
Enter the bus voltage required to reset the alarm.
Bus voltage rising above this level will clear the alarm.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an under-voltage condition. (default)
Send E-mail
: Checking this box will cause the unit to send a Bus Under-Voltage
alarm e-mail to the assigned address entered on the
E-mail Setup
page.
Bus A/B Over Voltage Alarm:
Over-Voltage Threshold:
Enter the bus over-voltage value. Bus voltage rising
above this level will trigger a Bus Over Voltage alarm.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over voltage condition. (default)
Send E-mail
: Checking this box will cause the unit to send a Bus Over-Voltage
alarm e-mail to the assigned address entered on the
E-mail Setup
page.
Bus A/B Over-Current Alarm: