Output Load Shedding:
Enable Load Shedding
: Check this box to disable this output when the bus
voltage drops below the load-shedding threshold for at least 30 seconds. This
feature can be used to disconnect less critical loads to preserve back-up
battery power as the battery voltage drops.
Load-Shedding Threshold
: Enter the voltage level at which the selected output
will be disconnected.
Load-Shedding Auto Recovery
: Check this box to allow the output to be
automatically reconnected when the bus voltage is above the
Auto Recovery
Threshold
for at least 60 seconds. The output must be manually re-enabled
using the
Output ON
button on the Status and Control page if the
Auto
Recovery
function is not enabled.
Auto Recovery Threshold
: Enter the voltage level at which the selected output
will automatically be reconnected. This value must be at least 0.5 volt above
the
Load-Shedding Threshold
voltage.
NOTE:
Outputs that have been disabled on the Status and Control Page will reconnect
automatically if Load-Shedding Auto Recovery is enabled for that output. To prevent this,
ensure that Load-Shedding Auto Recovery is not enabled.
Output Over-Current Alarm:
Over-Current Threshold
: Enter the over-current level. Output current above
this level for at least five seconds will trigger the Over-Current Alarm, and
disable the output (if feature enabled). Disable this alarm by setting the
threshold to zero amperes.
Activate Form-C Contact
: Checking this box will cause the Alarm relay to
trigger for an over-current condition.
Send E-mail
: Checking this box will cause the unit to send an output Over-
Current alarm e-mail to the assigned address entered on the
E-mail Setup
page.
Disable This Output:
Check this box to automatically disable the output for an
Over-Current condition on the selected output. This function may be used as
an electronic circuit breaker which can then be remotely reset by clicking the
Output ON
button on the Status and Control page.