5-6
5
TABLE 5-2 TROUBLESHOOTING GUIDE
CONTINUED
Possible
Symptom
Fault
Action or Check
Unit fails to respond
No delay after an
Provide a 70 ms minimum
or responds wrong
the address or
delay after changing an
after an address change address mode
address or address mode
or after an address
change
setting.
mode change
Insufficient delay
Program running on faster CPU
or in a compiled form runs
faster. Change delay routine to
a called time function that
tests the CPU clock.
Byte Data transfer fails Wrong command or
Start with short form
command syntax
commands: BIn? or BOn data.
i.e. BI1? or BO2 85 (55 HEX)
Wrong output value
Format setting
BOn commands use decimal
format.
PO command uses the
format set by the FORMat
command. Check the FORMat
command setting.
Wrong input data
Format setting
PI?, BI? and BIn? queries use
value
the format set by the FORMat
command. Check the FORMat
command setting.
Translation Table
If TABLE format selected,
values
check table values.
Data output did not
Output command
Data polarity takes place
respond to a polarity
not sent
with next output command.
command
Write a new value to the output
port.
For configured ports
Configure ports as inputs or
Polarity command
outputs before assigning
out of sequence
polarity.
Содержание 4807
Страница 5: ...ii This page left intentionally blank...
Страница 22: ...1 17 1 Figure 1 3 2367 CE Certificate...
Страница 69: ...2 40 2 This page left intentionally blank...
Страница 129: ...5 10 5 This page left intentionally blank...
Страница 159: ...A 30 A4 This page intentionally left blank...