ICP DAS WISE User Manual
http://wise.icpdas.com
206
Figure 10-10
:
AI Deadband Operation (< or <= a numerical value)
(c)
In the IF Condition, when AI
=
a numerical value:
Assuming the Deadband value is set to be 1 mA, and the
following statements are defined in the related logic Rule:
IF AI=9mA, THEN DO=ON, ELSE DO=OFF, that means,
when AI receives a signal between 8mA (9mA minus the
deadband value 1mA) and 10mA (9mA plus the
Deadband value 1mA), the DO channel will change to
ON immediately. However, when the AI channel value
exceed 10mA, or is lower than 8mA, the DO channel will
change to OFF, as shown in the following figure.
Figure 10-11
:
AI Deadband Operation (= a numerical value)
v
Click “OK” button to confirm the settings and return to the Rule
settings page.
10.1.1.6 AO
AO channel value from ICP DAS I/O Module can be included in the
IF condition statements; the editing page for AO Condition Setting is