tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
96
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.
Examples:
Command: @01RTT70R0104500
Response: !01-032.64
Reads the temperature associated with 104500 ohms
of type 70 of module 01, and the module returns a
value of –32.64 degree.
Command: @01RTT70R00801.2
Response: !01+072.62
Reads the temperature associated with 801.2 ohms of
type 70 of module 01, and the module returns a value
of 72.62 degree.
Related Commands:
Section 2.19 ~AAD, Section 2.20 ~AADT, Section 2.31
@AAGxTtt, Section 2.33 @AASxTttC(data)
Related Topics:
Section A.6 Thermistor
Notes:
The temperature scale is set using the ~AADT command
and can be read using the ~AAD command. See Sections
2.19 and 2.20 for details.