tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
33
2.1 %AANNTTCCFF
Description:
Sets the configuration of an analog input module.
Syntax
:
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
Address of the module to be configured in
hexadecimal format (00 to FF)
NN
New address of the module in hexadecimal format
(00 to FF)
TT
New type code, see Section 1.10 for details. Not
used by the tM-TH8. For the tM-TH8 use the
$AA7CiRrr command to set the type of each
channel, see Section 2.10 for details.
CC
New Baud Rate code, see Section 1.10 for details.
For the tM-TH8, the slide switch must be moved to
the INIT position in order to change Baud Rates.
See Section A.1 for details.
FF
Used to set the data format, checksum, and filter
settings (Section 1.10). For the tM-TH8, the slide
switch must be moved to the INIT position in order
to change the checksum setting. See Section A.1
for details.
tM-TH8
Содержание tM-TH8
Страница 8: ...tM TH8 User Manual Rev A1 1 7MH 018 A11 8 1 2 Terminal Assignment...
Страница 10: ...tM TH8 User Manual Rev A1 1 7MH 018 A11 10 1 4 Block Diagrams 1 4 1 Block Diagram for the tM TH8...
Страница 11: ...tM TH8 User Manual Rev A1 1 7MH 018 A11 11 1 5 Dimensions...
Страница 13: ...tM TH8 User Manual Rev A1 1 7MH 018 A11 13 1 7 Quick Start Please refer to the Quick Start Guide for tM TH8...
Страница 67: ...tM TH8 User Manual Rev A1 1 7MH 018 A11 67 Related Topics Section 1 9 Calibration tM TH8...