tM-TH8 User Manual, Rev: A1.1 7MH-018-A11
76
2.23 ~AAO(Name)
Description:
Sets the name of a module.
Syntax:
~AAO(Name)[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
O
Command to set the module name
(Name) New name of the module (max. 6 characters).
Response:
Valid command:
!AA[CHKSUM](CR)
Invalid command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is
incorrect, there is a communication error, or there is no
module with the specified address.